Datasheet
AC centrifugal module - RadiCal
®
backward curved, single inlet
with housing
K2E225-RA92-01
Charts: Air flow 60 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
qv[m^3/h]
1.6001.5001.4001.3001.2001.1001.0009008007006005004003002001000
qv[cfm]
9008007006005004003002001000
p f s[Pa]
750
700
650
600
550
500
450
400
350
300
250
200
150
100
50
0
pfs _E[IN H2O]
3,1
3
2,9
2,8
2,7
2,6
2,5
2,4
2,3
2,2
2,1
2
1,9
1,8
1,7
1,6
1,5
1,4
1,3
1,2
1,1
1
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0
p f s[Pa]
1
2
3
4
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
Measured values
1
2
3
4
U
V
230
230
230
230
f
Hz
60
60
60
60
n
min
-1
2900
2700
2700
2815
P
e
W
190
210
207
196
I
A
0.83
0.92
0.90
0.85
LpA
in
dB(A)
69
64
60
66
LwA
in
dB(A)
76
72
68
73
qv
m
3
/h
1300
1010
780
460
p
fs
Pa
0
200
350
500
U = Supply voltage · f = Frequency · n = Speed · P
e
= Power input · I = Current draw · LpA
in
= Sound pressure level inlet side · LwA
in
= Sound power level inlet side · qv = Air flow
p
fs
= Pressure increase
Item no. 11021-5-9980 · Revision 82063 · Release 2014-05-08 · Page 6 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com