Product Data Sheet REF100-11/12
02/01/2019 page 4 of 10
3 Operating Data
3.1 Electrical Operating Data
Measurement
conditions:
Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C; Motor axis horizontal; warm-up
time before measuring 5 minutes (unless otherwise specified). In the intake and outlet area
should not be any solid obstruction within 0,5 m.
∆p = 0:
corresp. to free air flow (see chapter aerodynamics)
I:
corresp. to arithm. mean current value
Features Condition Symbol Values
Voltage range U 8 V 15,0 V
Nominal voltage U
N
12,0 V
Power consumption 3,2 W 7,5 W 11,8 W
+- 17,5 % +- 12,5 % +- 15,0 %
Tolerance
∆p = 0
0010
P
Current consumption 435 mA 625 mA 785 mA
+- 17,5 % +- 12,5 % +- 15,0 %
Tolerance
∆p = 0
0010
I
Speed 3.750 1/min 5.200 1/min 6.100 1/min
+- 12,5 % +- 7,5 % +- 10,0 %
Tolerance
∆p = 0
0010
n
Starting current
consumption
1.800 mA
Measurement
conditions:
Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C; Motor axis horizontal; warm-up
time before measuring 5 minutes (unless otherwise specified).
In the intake and outlet area should not be any solid obstruction within 0,5 m.
∆p = 0: corresp. to free air flow (see chapter aerodynamics)
I: corresp. to arithm. mean current value
3.2 Electrical Features
Electronic function None
Reversed polarity protection Rectifying diode
Max. residual current at U
N
I
F
<= 10 mA
Locked rotor protection Auto restart
Locked rotor current at U
N
I
block
approx. 500 mA
Clock signal at locked rotor
t
3
/ t
4
typical: 0,38 s / 8,2 s