Datasheet

Product Data Sheet RER125-19/06
01/31/2019 page 6 of 9
3.2 Electrical Features
Locked rotor protection Impedance
Locked rotor current at
3.3 Aerodynamics
Measurement
conditions:
Measured with a double chamber intake rig acc. to DIN EN ISO 5801.
Normal air density = 1,2 kg/m3; Temperature 23°C +/ - 3°C;
In the intake and outlet area should not be any solid obstruction within 0,5 m. Motor shaft
horizontal.
The information is only valid under the specified test conditions and may be changed by the
installation conditions. If there are deviations from the standard test conditions, the
characteristic values must be checked under the installed conditions.
Measurement setup: Measured between two steel plates
Steel plate: 220 mm x 220 mm
Intake nozzle: D: 86 mm; R: 5 mm
Distance between bottom and top plate: 39 mm
Overlapping impeller / nozzle: 2 mm
a.) Operation condition:
2.600 1/min at free air flow Frequency: 50 Hz
Max. free-air flow (p = 0 /
= max.) 102,0 m3/h
Max. static pressure (p = max. /
=0) 115 Pa
b.) Operation condition:
2.900 1/min at free air flow Frequency: 60 Hz
Max. free-air flow (p = 0 /
= max.) 113,0 m3/h
Max. static pressure (p = max. /
=0) 150 Pa