Installation Guide

3
DANGER
Drilling holes in the vent
components is NOT permitted.
JOINT PROCEDURE
(see illustration #1 and images 1, 2 & 3 below)
The female end of each Z-Vent III component incorporates a silicone sealing gasket. Examine all components to insure that
gasket integrity has remained during shipping. Gaskets must be in the proper position or flue gases could leak resulting in carbon
monoxide poisoning.
1. Align pipes and push them together as far as they will go (to
indent or at least 1.75 inches).
2. Tighten gear clamp to a minimum torque of 40 in/lbs. and a
maximum of 50 in/lbs. Over tightening will cause seal to
fail. DO NOT use power tools when tightening gear
clamps
3. Proper pipe orientation is essential to achieve effective
condensate flow. In most cases the use of a flue collar
adaptor is required to connect directly to the appliance. This
adaptor will configure the vent orientation with the gasket end
of pipe and fittings towards termination.
NOTE: Some flue collars may require the use of high
temperature silicone sealant to make a positive
pressure gas tight seal.
IMAGES 1, 2, & 3
CLEARANCE TO COMBUSTIBLES
SIDE WALL VENTING INSTALLATION
(see illustration #2 and images 4 & 5 below)
1. Penetrating a combustible wall requires the use of a wall thimble. The pipe may be mortared in directly without using a
wall thimble, if the wall is non-combustible. Install wall thimble into wall, observing the aforementioned rules and/or local
building codes. Select the point of wall penetration where the minimum ¼” per foot of slope (6.4 mm per 305 mm) can
be maintained. A framed opening is required to insert the thimble halves. The thimble is adjustable for different wall
thicknesses. Caulk around outside edge of plates as necessary and fasten to wall using suitable screws or nails. The vent
pipe must be sealed at wall thimble as per code regarding continuous vapor barrier.
SYSTEM OPERATING
TEMPERATURE
CLEARANCE
ENCLOSED
CLEARANCE
UNENCLOSED
HORIZONTAL VERTICAL HORIZONTAL VERTICAL
300°F (149°C)
8” (200 mm) 4”(100 mm) 1”(25 mm) 1” (25 mm)
480°F (249°C)
8”(200 mm) 4”(100 mm) 1” (25 mm) 1” (25 mm)