46 Meter Operation
Standard Procedures
The following are the standard meter procedures that can be selected for inclusion in
the event log, when the status event Procedure Invoked is also selected.
Procedure Name Description
4 Reset List Pointers Changes the number of unread records for load profile,
self-read, or when the event log is set to zero, and clears
the selected list.
5 Update Last Read Entry Changes the number of unread records for load profile,
self-read or event log.
10 Set Date and Time Sets initial meter UTC date and time and adjusts for DST
and time zone settings.
12 Activate all Pending Tables Activates all pending tables.
13 Activate Specific Pending Tables Activates specified pending tables (such as a pending
TOU calendar).
14 Clear all Pending Tables Clears all pending tables.
15 Clear Specific Pending Tables Clears specified pending tables.
Manufacturer Procedures
The following are the meter manufacturer procedures that can be selected for
inclusion in the event log, when the status event Procedure Invoked is also selected.
Procedure Name Description
2048 Self Calibration The manufacturer self-calibration procedure started.
2049 Flash Refresh Erases the flash and reprograms it with the currently
executing code. A meter reset is invoked.
2050 Disconnect and Control Relay
Command
Used to change the state of the load disconnect or control
relay – forcing them open overrides the auto-determination
of output state setup via provisioning. Invoking the
procedure to close them either performs that action or, if
activated via the provisioning program, returns back to the
auto-determination state.
2051 Clear Alarms Used to clear some or all of the meter alarms.
2056 Erase Code Bank Used to erase memory for meter software updates.
2057 Download Code Packets Used to download a new software image to the meter.
2058 Switch Code Bank Switches to the code bank that is not currently in use.
2059 Configure/Reset Load Profile Used to configure and erase the load profile.
2060 Record Self-Read Used to perform an instantaneous Self-Read.
2061 Write Single Bit in Table Used to modify a single bit in a single byte in a table.
2063 Force Tariff Used to set meter into a specific tariff period, either
indefinitely or until the next regularly scheduled change.