Instruction Manual
i.LON 100 Internet Server Programmer’s Reference  7-11 
Property Description 
<SCPThystHigh1> 
<SCPThystHigh2> 
<SCPThystLow1> 
<SCPThystLow2> 
When an alarm occurs based on one of the offest limits described above, the 
value of the input data point must reach the hysteresis value for that limit 
before the alarm can be cleared, and another alarm can be generated based 
on that offset limit. 
This allows you to set up an Alarm Generator that will trigger an alarm 
once each time the value of the input data point reaches a certain level, as 
opposed to multiple times (which would occur each time the data point was 
updated and its value remained within the range specified by the offset 
limit). 
Enter a scalar value for each of these properties. These values define the 
hysteresis level that will be used for each alarm offset limit. For a more 
detailed description of the hysteresis fields and how they relate to the 
offset limit values, see Hysteresis Levels and Offset Limits on page 7-13. 
If you use the i.LON 100 Configuration Software to modify the 
configuration of an Alarm Generator after creating it with the SOAP/XML 
interface, all four hysteresis properties will be reset to the value chosen for 
<SCPThystHigh1>. 
NOTE: If you use the AlarmGeneratorGet function to return the 
configuration of an Alarm Generator whose input data point uses the 
format type SNVT_temp_p#US or SNVT_temp#US, then the values of 
these properties will be displayed using the SNVT_temp_f#US format. This 
rule applies to all formats that use the #US specifier. 
7.2.1.2.1  Alarm Priority Levels 
You can select a priority level for the Alarm Generator by filling in the 
<UCPTalarmPriority> property. When doing so, you must reference each priority level with 
the identifier listed in Table 23. 
Each time an Alarm Generator generates an alarm, the priority_level field of the alarm data 
points chosen for the Alarm Generator will be updates to the priority level chosen here.
Table 23  Alarm Priority Levels 
Identifier Notes 
PR_LEVEL_0  Lowest alarm priority level 
PR_LEVEL_1 
PR_LEVEL_2 
PR_LEVEL_3  Highest alarm priority level 
PR_1  Life Safety Fire Alarms 
PR_2  Property Safety Fire Alarms 
PR_3  Fire Supervisory Alarm 
PR_4  Fire Trouble/Fault (Display) 
PR_6  Fire Pre-Alarm, HVAC Critical Equipment Alarm 
PR_8  HVAC Alarms (BACnet Priority 8) 










