<OutputDataPoint> 
This element defines the output data point for this function block. 
You must specify the <UCPTpointName> assigned to the output data point 
within this element. The value of this data point will be updated with the 
result of each comparison or statistical operation that the Analog Function 
Block performs. 
9.2.1.2.1 Output Functions 
Table 46 lists and describes the output functions you can use to fill in the 
<UCPToutputFunction> property. You must reference each function by the identifier listed 
in the table. 
The function selected here determines the value that the Analog Function Block will assign 
to the output data point. 
Table 46  Output Function Identifiers 
Identifier Value Assigned To The Output Data Point 
FN_MAX 
Maximum value of all input data points. 
FN_MIN 
Minimum value of all input data points. 
FN_SUM 
The sum of the values of all input data points. 
FN_AVERAGE 
The average of the values of the input data points. 
FN_COMPARE 
The result of the last comparison between the input data point(s) and the 
compare data point (or the value assigned to the <UCPTtrueThreshold> 
property, if it is defined). If this is selected, you must also select a comparison 
function by filling in the <UCPTcompFunction> property. 
For an example of how you could use this function, see FN_COMPARE 
Example on page 9-12. 
FN_AND 
This function reports True when all the input data points are True. The 
definition of a True input depends on the data point type. If the input type is 
SNVT_switch, the input is True if the value and state fields are non-zero. If the 
input type is a structure other than SNVT_switch, the Boolean threshold is 
undefined, and FN_AND should not be used. 
If the input data point(s) type is a scalar or enumeration value, the function 
reports True if all the comparisons made by the comparison function for the 
analog function block are True. For an example of how you could use the 
FN_AND output function in this way, see FN_AND Example on page 9-11. 
FN_OR 
This function reports True when any of the input data points are True. The 
definition of a True input depends on the data point type. If the input type is 
SNVT_switch, the input is True if the state and value fields are non-zero. If 
the input type is a structure other than SNVT_switch, the Boolean threshold is 
undefined, and FN_OR should not be used. 
If the input data point(s) type is a scalar or enumeration value, the function 
reports True if any of the comparisons made by the comparison function for the 
analog function block are True. For an example of how you could use the 
FN_OR function in this way, see FN_OR Example on page 9-12. 
i.LON 100 Internet Server Program9-10  mer’s Reference 