Instruction Manual
The 16 SNVT_switch data points to be translated are defined by a list of <InDataPoint> 
elements. Each element must contain two properties: <UCPTpointName> and 
<UCPTindex>. The <UCPTpointName> must identify a SNVT_switch data point. The 
<UCPTindex> must be in the range 0-15. 
The value of the state field  of each input data points will be read and stored in bitX of the 
output data point, where X represents the <UCPTindex> selected for the input data point. 
For example, the state field of the data point assigned index number 0 in the Type Translator 
would be stored in Bit0 of the output SNVT_state data point. Or, the state field of the data 
point assigned index number 8 would be stored in Bit7 of the output SNVT_state data point. 
If any of the index numbers for the input data points are not used (meaning that less than 16 
data points were supplied to the Type Translator), then the corresponding field in the output 
data point will be assigned a value of 0. 
12.2.1.2.1.2 SNVT_lev_disc_TO_SNVT_occupancy 
Use this Type Translator Rule to translate an input data point of type SNVT_lev_disc to an 
output data point of type SNVT_occupancy. When you use this rule, you must reference the 
SNVT_lev_disc data point that is to be translated by its <UCPTpointName> in the 
<InDataPoint> element. You must reference the SNVT_occupancy data point to store the 
result of the translation by its <UCPTpointName> in the <OutDataPoint> element. 
Each time a type translation is made, the Type Translator will assign the SNVT_occupancy 
output data point an enumeration value based on the enumeration assigned to the input 
data point. The enumeration values assigned to the output data point follow the rules 
described in Table 62. 
Table 62  SNVT_lev_disc_TO_SNVT_occupancy 
If the Input SNVT_lev_disc Data Point Is.....  Then the SNVT_occupancy Output Data 
Point Will Be Set To... 
ST_NUL OC_NUL 
ST_OFF OC_UNOCCUPIED 
ST_ON OC_OCCUPIED 
ST_HIGH OC_BYPASS 
ST_LOW OC_STANDY 
ST_MED OC_STANDY 
12.2.1.2.1.3 SNVT_lev_disc_TO_SNVT_switch 
Use this Type Translator Rule to translate an input data point of type SNVT_lev_disc to an 
output data point of type SNVT_switch. When you use this rule, you must reference the 
SNVT_lev_disc data point that is to be translated by its <UCPTpointName> in the 
<InDataPoint> element. You must reference the SNVT_switch data point to store the result 
of the translation by its <UCPTpointName> in the <OutDataPoint> element. 
Each time a translation is made, the Type Translator will assign the SNVT_switch output 
data point a value that is based on the enumeration currently assigned to the input data 
point. The values assigned to the output data point follow the rules described in Table 63. 
i.LON 100 Internet Server Program12-8  mer’s Reference 