Instruction Manual
i.LON 100 Internet Server Programmer’s Reference 
If the SNVT_scene Input Field Values 
Are…. 
Then the SNVT_setting Output Field Values Are…. 
function scene_number function  setting  Rotation 
SC_RECALL 2  SET_STATE 50  0 
SC_RECALL 3  SET_STATE 75  0 
SC_RECALL >3  SET_NUL 100  0 
SC_NUL N/A  SET_NUL 100  0 
12.2.1.2.1.6 SNVT_scene_TO_SNVT_switch 
Use this Type Translator Rule to translate an input data point of type SNVT_scene to an 
output data point of type SNVT_switch. When you use this rule, you must reference the 
SNVT_scene data point that is to be translated by its <UCPTpointName> in the 
<InDataPoint> element. You must reference the SNVT_switch data point to store the result 
of the translation by its <UCPTpointName> in the <OutDataPoint> element. 
Each time a translation is made, the SNVT_switch output data point will be assigned a value 
and state based on the values assigned to the function and scene_number fields of the 
SNVT_scene input data point. The value assigned to the output data point follow the rules 
described in Table 66. 
Table 66  SNVT_scene to SNVT_switch 
If the SNVT_scene Input Field Values Are.... 
scene_number 
Then the SNVT_switch Output Data Point Will Be 
Set To... 
SC_NUL N/A*  0.0 0 
SC_RECALL 1  25.0 1 
SC_RECALL 2  50.0 1 
SC_RECALL 3  75.0 1 
SC_RECALL >3  100.0 1 
SC_RECALL 255  0.0 0 
function 
*If the input function is SC_NUL and the input scene_number is 0, the value of the output data point 
will not be modified. 
12.2.1.2.1.7 SNVT_setting_TO_SNVT_switch 
Use this Type Translator Rule to translate an input data point of type SNVT_setting to an 
output data point of type SNVT_switch. When you use this rule, you must reference the 
SNVT_setting input data point that is to be translated by its <UCPTpointName> in the 
<InDataPoint> element. You must reference the SNVT_switch data point to store the result 
of the translation by its <UCPTpointName> in the <OutDataPoint> element. 
Each time a translation is made, the SNVT_switch output data point will be assigned a value 
based on the values assigned to the function and setting  fields of the SNVT_setting input 
data point. The value assigned to the output data point follow the rules described in Table 
67. 
Table 67  SNVT_setting_TO_SNVT_switch 
If the SNVT_setting Input Field Values Are.... 
Function setting 
Then the SNVT_switch Output Data Point Will Be 
Set To... 
12-10 










