Instruction Manual
4.5 Data Formatting 
In order to keep the i.LON SOAP/XML interface neutral across regions, most of the rules for 
formatting data, which would normally be changeable in LNS, are not changeable on the 
i.LON 100. The one exception is the support of measurement system locale which is new in 
version 1.1. The following list describes the various regional settings used by the i.LON 100 
SOAP / XML interface: 
Decimal Symbol – Always period "." 
Precision – Single floats always use 7 digits of precision, including digits before and after 
the decimal point. Double floats always use 14 digits of precision. For the rest of the base 
types, precision is determined by the type definition 
Digit Grouping Symbol – Always comma "," 
Digit Grouping – Always in the form "123,456,789" 
Negative Sign Symbol – Always the minus sign "-" 
Negative Number Format – Always "-1.1"; negative symbol in front, and no space between 
the symbol and the number 
List Separators – If the format uses the localized list separator symbol verticle bar "|", the 
i.LON 100 will replace it with comma ",". However, if you define a new type in the 
NodeBuilder Resource Editor which is a structure, array or union, the default list separator 
is space " ". The localized list separator must be explicitly specified in the format. 
Measurement System – The i.LON 100 does not use localization settings for measurement 
system. The measurement system used to display a formatted value is determined by the 
UCPTformatDescription property of the data point. For example, if you have a data point 
whose format is defined as SNVT_temp_f#US, then the UCPTvalue written to the 
DataServerRead SOAP message will be in Farenheit. If that data point is an input to the 
AlarmGenerator, then the format of a property which specifies a comparison value, a delta or 
an offset like UCPThighLimit2Offset will also be in US units when you read it with the 
AlarmGeneratorGet function. Furthermore, you must use US units when setting the 
property with the AlarmGeneratorSet function. You should note that the value stored in the 
XML file will always be in SI units so that XML files may be shared between i.LON 100s. 
The rule used by the applications is that the format of the primary data point for the 
application instance determines the format of measurement system dependent properties, 
like offsets, comparison values and deltas. 
i.LON 100 Internet Server Program4-10  mer’s Reference 