Instruction Manual
i.LON 100 Internet Server Programmer’s Reference 
Property Description 
<UCPTalarmClrTime> 
Specifies the time period to wait after the condition that caused an alarm 
has returned to normal status before the alarm will be cleared. You must 
use the following format for this property: 
DAYS HOURS:MINUTES:SECONDS.MILLISECONDS 
For example, 0 6:22:12.333 indicates a time period of 6 hours, 22 minutes 
and 12.333 seconds. The maximum value you can enter is: 
0 1:59:59.999 
The default value is: 
0 00:00:00.000 
<UCPTlowLimit1Offset> 
<UCPTlowLimit2Offset> 
<UCPThighLimit1Offset> 
<UCPThighLimit2Offset> 
Enter a scalar value for each of these properties. These values will be used 
as the offset limits for the Alarm Generator when the 
<UCPTcompFunction> property is set to FN_LIMIT. In this case, alarms 
will be generated when any of the following conditions are true: 
•  Value of Input Data Point> Value of Compare Data Point +highLimit1Offset 
•  Value of Input Data Point > Value of Compare Data Point +highLimit2Offset 
•  Value of Input Data Point < Value of Compare Data Point – lowLimit1Offset 
•  Value of Input Data Point < Value of Compare Data Point – lowLimit2Offset 
The value entered for <UCPThighLimit2Offset> must be greater than that 
entered for <UCPThighLimit1Offset>, and the value entered for 
<UCPTlowLimit2Offset> must be less than that entered for 
<UCPTlowLimit1Offset>. The default value for each property is 0. If any of 
these properties are left empty, they will not be used to check for alarm 
conditions. When you set these properties, you must also set the 
corresponding hysteresis properties, which are described later in the table. 
Each alarm condition caused by the offset properties will cause the 
<UCPTpointStatus> of the input data and alarm data points to be set to a 
different status. For more information on this, see see Hysteresis Levels 
and Offset Limits on page 7-13. 
NOTE: If you use the AlarmGeneratorGet function to return the 
configuration of an Alarm Generator whose input or compare data points 
use the format type SNVT_temp_p#US or SNVT_temp#US, then the 
values of these properties will be displayed using the SNVT_temp_f#US 
format. This rule applies to all formats that use the #US specifier. 
7-10 