User`s guide
i.LON SmartServer 2.0 Programming Tools User’s Guide  215   
AL_FIR_MONITOR_COND  =20 
AL_FIR_MAINT_ALERT  =21 
AL_FATAL_ERROR  =30 
AL_ERROR =31 
AL_WARNING  =32 
AL_HEADER =243 
AL_FOOTER =244 
AL_DEBUG  =245 
AL_INFO =246 
AL_SYSTEM_INFO =250 
AL_VALUE_INVALID =251 
AL_CONSTANT =252 
AL_OFFLINE =253 
AL_UNKNOWN  =254 
AL_NUL  =255 
EXAMPLE 
FPM::Dp::PointStatus nviSetPoint_status; 
nviSetPoint_status = 
nviSetPoint.GetDpPropertyAsPointStatus(FPM::Dp::dataUCPTstatus); 
  printf ("nviSetPoint status = %d \n \n", nviSetPoint_status); 
Note: Using this data point property method extensively may significantly impact the performance 
of the SmartServer; therefore, it is recommended that you use it sparingly. 
GetDpPropertyAsInt(UCPTpriority) 
You can use the GetDpPropertyAsInt(UCPTpriority) method in the Work()and 
OnTimer()routines of an FPM application to read the current priority of a data point. 
Note: The use of the GetDpPropertyAsInt(UCPTpriority) method is not recommended. 
SYNTAX 
int GetDpPropertyAsInt(FPM::Dp::dataUCPTpriority) 
The FPM::Dp::dataUCPTlastupdate parameter specifies the UCPTpriority configuration 
property of the data point. The UCPTpriority configuration property is a short that indicates the 
current priority level assigned to the data point, where 0 is the highest priority, and 255 is the 
lowest. 
EXAMPLE 
int nviSetPoint_priority; 
nviSetPoint_priority = 
nviSetPoint.GetDpPropertyAsInt(FPM::Dp::dataUCPTpriority); 
printf ("nviSetPoint priority = %d \n", nviSetPoint_priority); 
SetDpProperty (UCPTAliasName) 
You can use the SetDpProperty(UCPTAliasName) method in the Work()and 
OnTimer()routines of an FPM application to write an alias name to a data point. This method 
updates the UCPTAliasName configuration property of the data point. 
SYNTAX 