User`s guide
62  Creating FPM Device Interface (XIF) Files 
 nciHeartbeat[0],nciOffline[0],nciThrottle[0],nciHysteresis[0] 
 }; 
/////////////second FB array instantiated////////////////////////// 
network input SNVT_switch nviACSwitch[NUM_SWITCH_ENCODER_FBs]; 
network input SNVT_switch nviFurnaceSw[NUM_SWITCH_ENCODER_FBs]; 
network output SNVT_hvac_mode nvoHVACMode[NUM_SWITCH_ENCODER_FBs]; 
fblock UFPTSwitchEncoder { 
nviACSwitch[0] implements nviACSwitch; 
nviFurnaceSw[0] implements nviFurnaceSwitch; 
nvoHVACMode[0]implements nvoHVACMode; 
} fbSwitchEncoder[NUM_SWITCH_ENCODER_FBs] external_name ("Digital 
Encoder"); 
Multiple Functional Blocks with Multiple UFPTs and Same Data Point Names 
The following example demonstrates how to use multiple functional block arrays in a model file to 
create multiple sets of functional blocks that are instances of their respective UFPTs. In addition, this 
example handles the scenario in which the data points in a UFPT have the same names. You could 
then write separate FPM applications for the UFPTs instantiated by the model file. When you deploy 
the FPM applications on the SmartServer and select the XIF generated from this model file, the 
internal FPM device will include arrays of the functional blocks that are separate instances of their 
respective FPM applications. 
#define NUM_OF_ADD_FB 3 
#define NUM_OF_SUB_FB 2 
/////////////first FB array instantiated///////////////////////// 
network input SNVT_count in1[(NUM_OF_ADD_FB + NUM_OF_SUB_FB)]; 
network input SNVT_count in2[(NUM_OF_ADD_FB + NUM_OF_SUB_FB)]; 
network output SNVT_count out1[(NUM_OF_ADD_FB + NUM_OF_SUB_FB)]; 
fblock UFPTMathAdd { 
in1[0] implements in1; 
in2[0] implements in2; 
out1[0] implements out1; 
} fbMathAddFunction[NUM_OF_ADD_FB] external_name ("FpmAdd"); 
/////////////second FB array instantiated///////////////////////// 
fblock UFPTMathSubtract { 
in1[NUM_OF_ADD_FB] implements in1; //can't use [0] for second FB 
in2[NUM_OF_ADD_FB] implements in2; //so use next unused index 
out1[NUM_OF_ADD_FB] implements out1; 
} fbMathSubtractFunction[NUM_OF_SUB_FB] external_name ("FpmSub"); 
Saving your Model File 
When you have finished creating your model, you need to save it as a Neuron C source file (.nc 
extension) on your computer. The example above is stored in a model file named “HVAC.nc” in a 
folder named “ModelFile” that has been created under the C:\LonWorks directory. The file path of the 
source file in the example is therefore C:\LonWorks\ModelFile\HVAC.nc. You can then proceed to the 