Applying Power to the MPR-50 Multi-Port Router 
Connect earth ground, if available, to terminal 3. Then connect 9–28VAC (40–70Hz) 
or 9–35VDC power to terminals 1 and 2—the power terminals are polarity-
insensitive so the polarity of the DC input is unimportant. The green Power LED 
will illuminate to indicate the unit is powered and the Status LEDs will begin 
operating within seconds. 
Attaching the Router to a LONWORKS Network 
Connect the screw terminals marked Router 1 through Router 5 to the desired 
channels. Router 1 is for the TP/XF-1250 channel, while Routers 2–5 are for the 
TP/FT-10 channels. TP/XF-1250 and TP/FT-10 channel wiring is polarity-
insensitive, and the TP/FT-10 connections are link power compatible. Any router 
that is not going to be used may be left unconnected. 
Figure 2.4 Router Connections for the Multi-Port Router 
For complete information about acceptable wire types, maximum stub lengths, 
termination requirements, and cable vendors, consult the Junction Box and 
Wiring Guidelines for Twisted Pair 
LONWORKS Networks Engineering Bulletin 
available from Echelon’s Web site. 