Owner manual
LED Legends 
The Power LED will illuminate whenever power is connected to the MPR-50. 
The following two tables describe the behavior of the Status LEDs for the Monitor 
and for Routers 1–5. For easy reference, shortened versions of the Status LED 
legends are printed on the front panel of the MPR-50. 
The Status LEDs illuminate as green, orange, and yellow. When yellow is displayed, 
orange and green may appear illuminated together depending upon the lighting 
conditions. 
Table 2.1 Monitor Status LED Legend 
Color Description 
Off  No power to MPR-50. 
Green on steadily  The Monitor and Routers 1–5 are configured. Since 
power-up, no errors have been logged for Routers 1–5 
or their externally connected channels. 
Green slow flashing  Repeater mode.  Routers 1–5 will repeat all valid 
traffic. This mode is useful for plug ‘n play use without 
network management tools. 
Slow flashing is defined as on-for-one-second/off-for-
one-second. 
Yellow on steadily  Monitor is offline. All of the router Status LEDs will 
also be yellow on, although the routers will still be 
routing if they were previously configured to do so. 
The router Status LEDs are yellow on since the 
Monitor, being offline, is unable to determine the states 
of the routers. 
Yellow slow flashing  Monitor has not been commissioned. Slow flashing is 
defined as on-for-one-second/off-for-one-second. The 
router Status LEDs continue to indicate the current 
status for their associated routers and attached 
channels. 
Orange fast flashing  Router alarm condition(s) logged. 
Fast flashing is defined as on-for-one-half-second/off-
for-one-half-second. 
8  MPR-50 Multi-Port Router Hardware and Software