User`s guide

The NODEUTIL node utility application, available on Echelon’s web site, can be used
to modify the MIP mode buffer configuration from a PC host.
See the README.TXT
file included with NODEUTIL for details.
By default, the SLTA-10 NSI-mode program ID consists of 8 bytes of program
identification information (80-00-Ol-Ol-03-00-xx-3C, where ‘xx’ is determined by the
transceiver being used). The host application must change this program ID to
indicate its application. This is done automatically in LNS by the LCA Object
Server. If not using the LCA Object Server, the host application needs to send local
write-memory network management messages to change the program ID.
See the
LNS Host API Programmer’s Guide
for further information.
Table 4.5 SLTA-10 Adapter NSI-mode Default, and Minimum, Buffer Configuration
NSI-mode Buffer Parameter
Default Count
Default Size Default Total
in Bvtes
Bytes
IR
eceive transaction buffers
I 16
I 13 I 208
1 Transmit transaction buffers
I
I
28
I
Application input buffers 3
255 765
Application output buffers 3
255 765
Network input buffers 2
66 132
Network output buffers 2
66 132
Priority app. output buffers 3
255 765
Priority net. output buffers 2
66 132
Total bytes used for buffers
2955
SLTA-10 Adapter User’s Guide
4-9