User Manual
DC Voltage 
Source
Inductive Load
DC +
DC -
Inductive Load
AC Line
AC Neutral
SSR
- Control +
Output
Load 
Resistor
5 6 7 8
AC Voltage 
Source
Switched AC Line
Switched DC +
Pulse Meter Inputs 
The SmartServer includes two impulse meter inputs that comply with the DIN 43 864 impulse standard 
(open terminal voltage <12VDC, maxi mum c urrent ≤27mA).  The pulse meter input connections are 
implemented on screw terminals 9–12: Meter 2 is connected to terminals 9-10; Meter 1 is connected to 
terminals 11-12. These connections are polarity-sensitive: terminals 9 and 11 are marked negative (-), 
and terminals 10 and 12 are marked positive (+).  You cannot reverse the polarity of the pulse meter 
inputs because it will cause improper operation of the measure ment circuits. 
Each of the pulse meter inputs is controlled b y a Pulse Counter a pplication on the S martSer ver. A 
pulse input meter registers a p ulse when the circuit between its p ositive and negative conn e c tions is 
closed (the voltage is 0) for 30ms or longer. The circuit must be open for a minimum of 30ms between 
pulses. See Chapter 9 of the SmartServer 2.2 U ser’s Gui de for c onfiguring the SmartServer t o use the 
pulse meter inputs to which it is connected. 
The following figure illustrates the locatio n of the pulse meter input screw terminals on t he 
SmartServer. 
SmartServer 2.2 Hardware Guide  15 