Instruction manual

26
Symptom Reason Action
Alarm: No re/fuel Lack of re Rell hopper acc. to point „Lightning up”
Boiler
cannot reach
programmed
temp.
Wrong lightning up Check „Lightning up”
Too moisture pellet
Check moisture – use pellet with required
parameters
Clogged primary air channels Call service – after-warranty service
Clogged heat exchanger’s pipes
Clean pipes or call service – after warranty
service
Damaged gasket on blower’s or
burner’s ange
Replace – after-warranty service
Damaged blower Replace – after-warranty service
Boiler is fuming
Clogged or unproper chimney Get the chimney-sweeper opinion
Strong wind forces fumes into the
chimney
Consider installation of devices regulating
chimney draught
Door is fuming
Gasket leak Regulate the door’s hinges
Damaged rope Replace the rope – after-warranty service
Controller doesn’t
work
No voltage in the grid
Check the protection devices in the electric
installation
Damaged wire Wire and connection control
Damaged controller Call the service
Loud blower
operation
Damaged bearings Call the service - replace the blower
Damaged capacitor Call service – replace the capacitor
Loosen xing of blower Fixing control, screw in
Dirty rotor blades Control, cleaning
11. Troubleshooting