User's Manual
in longer cycle times. The temperature range
is adjustable from 0.5 to 3 °F (0.3 to 1.7 °C) in
0.5°F (0.3°C) increments. The default oset is
0.5°F (0.3°C).
If the Indoor Unit is AC only and an auxiliary
heater is congured, this option appears under
the Aux Heat Settings menu.
Heat Dissipation Time The amount of time
the fan will run after the heat set point has
been reached and the call for heat has been
turned o. Running the fan for a period
of time allows for heated air to circulate
throughout the home. The time is adjustable
from 0 to 900 seconds (default is 0 seconds).
If the Indoor Unit is AC only and an auxiliary
heater is congured, this option appears under
the Aux Heat Settings menu.
Indoor Unit Temp Oset Depending on its
type, the Indoor Unit uses a temperature
oset for the heating set point, taking
into consideration the higher sensing
temperature. The Daikin ENVi thermostat
applies the oset to the set point which is
sent to the Indoor Unit. The oset should be
3.5°F (2.0°C) for wall-mounted and ducted
indoor units, and 0°F (0°C) for oor-standing
indoor units (available in the future). The
oset range is adjustable from 0°F (0°C) to
5.5 °F (3.0°C) in 0.5°F (0.3°C) increments to
allow for future indoor unit expansions. The
default oset is 3.5°F (2.0°C).
Heat Pump to Aux Temp Delta The
minimum dierence between the current
temperature and the set temperature that
will activate Aux Heat (regardless if the
maximum run time of the heat pump was
18