Specifications

Size 20 30 35
B box C box
m3/h 3600 4500 6300
KW 21,7
26,8 35,5
kW 21,2
26,0 34,5
kW
7,2 9,6 12,9
A 17,9 21,6
29,7
-
5,8 5,4 3,5
-
3,02 2,79 2,76
- 2,95 2,71 2,68
KW 21,4
25,6 35,2
KW 20,9 24,8 34,2
kW 7,2 9,2 12,9
-
2,97 2,78 2,74
- 2,90 2,69 2,65
KW
20,5 24,9 35,6
kW
20,0 24,1 34,6
kW 6,79 8,45 11,43
- 2,95 2,85 3,03
-
3,02 2,95 3,12
50%
22,7
5,9
3,83
kW S / H 18.6 / 30.7 18.6 / 30.7 18.6 / 42.8
kW S / H 20 / 33 20 / 33 20 / 46
% 93 93 93
m3/h S / H 1.9 / 3.2 1.9 / 3.2 1.9 / 4.5
1xZP83KCE 1xZP103KCE
ZP72KCE + ZP72KCE
1 x TXV 1 x TXV 1 x TXV
1 x 6.3 1 x 6.3 1 x 8.2
0.63 / 4 / 14 0.63 / 4 / 14 0.875 / 4 / 14
1.1 / 3 / 16 1.1 / 3 / 16 1.54 / 3 / 16
Application Guide BALTIC - 0108 • 17 •
GENERAL DATA
BAC = Cooling only rooftop BAH = Heat pump rooftop BAG =CoolingonlywithgasredheatingBAM=Heatpumprooftopwithgasredheating
(1)AlldataareatEuroventconditionat400V/3Ph/50Hz.Summer : Outdoor temperature 35°C DB / Entering coil temperature
27°CDB/19°CWB.(2)excludingheatingemissionofthesupplymotorfan.(3)includingheatingemissionofthesupplymotor
fan. Winter:Outdoortemperature7°CDB,6°CWBEnteringcoiltemperature20°CDB.(4)AtnominalAirow.(5)S=Small,H
=Hight.(6)atdownreturnairanddownsupplyairconguration.(7)belowthisvalue,option"Lowambiantkit"isrequired
Table 1.1
Performance
NominalAirow
Cooling BAC-BAG
GrossCoolingcapacity(1)
Net Cooling capacity
Power input BAC
Full load amps
Direct start up amps ratio Id / Ia
COPgrossBAC(3)
COPnetglobalBAC(2)
Cooling BAH-BAM
GrossCoolingcapacity(1)
Net Cooling capacity
Power input BAH
COPgrossBAH(3)
COPnetglobalBAH(2)
Heating BAH-BAM
Netheatingcapacity(1)
GrossHeatingcapacity(1)
Power input BAH
COPgrossBAH(3)
COPnetglobalBAH(2)
Part Load BAH-BAM(11)
PARTLoad%
Gross Cooling capacity in PART LOAD
Power input BAC in PART LOAD
COP gross cooling at part load
Heating - gaz red
Heating capacity
Input(stdheat/highheat)
Thermalefciency
GAZow(fornaturalgazat20mbarand15°C)
Refrigeration circuit
Nb of Circuits x Compressor type nb x type
SINGLE SINGLE TANDEM
Expansion nb x type
Refrigerant charge per circuit Clim / PAC kg
Coils
Indoor Coil : Face area / nb of rows / Fin per inch m2 / nb / FPI
Outdoor Coil : Face area / nb of rows / Fin per inch m2 / nb / FPI