Specifications
• 66 • Application Guide • BALTIC - 0108
{
{
{
{
ELECTRICAL DATA
STANDARD
Logical Output Board (1output:1assigned)
DO 1 - Alarm, General
Logical Input Board (4inputs:2assigned,2customized)
DI 1 - ON/OFF
DI 2 - Reset alarm
DI 3 & 4 - Customized
(choose,foreachinput(2)betweenthose12possibilities)
- Disable, Compressors & Heaters
-Disable100%Compressors
-Disable50%Compressors
- Disable, Heaters
- Disable, Cooling
- Disable, Heating
-Faultcontact,Humidier
- All return air
-20%Freshair
-30%Freshair
-40%Freshair
-50%Freshair
- All fresh air
- Activation A zone
- Activation B zone
- Activation C zone
- Activation Unoccupied zone
- Activation BMS zone
- Free, for BMS
ADVANCED CONTROL PACK OR TCB
Logical Output Board (4outputs:0assigned,4customized)
DO 3 to 6 - Customized
(choose,foreachinput(4)betweenthose7possibili-
ties)
- Alarm, Filters
- Alarm, Blower
- Alarm, Compressors
- Activation Gas
- Alarm, Heaters
- Alarm, Hot Water Coil Freezing
- Smoke alarm
- Heating mode
- Activation A zone
- Activation B zone
- Activation C zone
- Activation Unoccupied zone
- Activation BMS zone
- Free, for BMS
Logical Input Board (4outputs:0assigned,4customized)
DI 5 to 8 - Customized
(choose,foreachinput(4)betweenthose12possibilities)
- Disable, Compressors & Heaters
-Disable,100%Compressors
-Disable,50%Compressors
- Disable, Heaters
- Disable, Cooling
- Disable, Heating
-Faultcontact,Humidier
- All return air
-20%Freshair
-30%Freshair
-40%Freshair
-50%Freshair
- All Fresh Air
- Activation A zone
- Activation B zone
- Activation C zone
- Activation Unoccupied zone
- Activation BMS zone
- Free, for BMS
Analogue Input Board (4outputs:0assigned,2customized)
AI 1 & 2 - Customized
(choose,foreachinput(4)betweenthose4possibilities)
-Overrideroomtempsetpoint-5+5°C(4-20mA)
-Overridemin.freshairsetpoint0-100%(4-20mA)
- Weather sensor, Temperature
- Weather sensor, Humidity
-Freetemperature(NTCprobe)
-Freerelativehumidity(4-20mA)
CONTROL VARIABLES
Those contacts
add up
Those contacts
add up