Specifications

• 72 • Application Guide BALTIC - 0108
DS50
R/W L 3111
R/W L 3112
R/W L
3933
R/W L
R L 1000
R L 2315
R L 2516
R L 2517
R L 2526
R L 2527
R L 2536
R L 2537
R L 2546
R L 2547
R L 2615
R L 2616
R L 2617
R L 2625
R L 2626
DS50
R/W 1 = 1 s 3932
R/W 10 = 1,0°c
3322
(BMS)
R/W 10 = 1,0°c
3323
(BMS)
R/W 1=1%
3312
(BMS)
R/W 10 = 1,0°c
3322
(Uno)
R/W 10 = 1,0°c
3323
(Uno)
R/W 1=1%
3341
(BMS)
R/W 1=1%
3342
(BMS)
R/W 1 = 1h 3121
R/W 1 = 1m 3122
R/W 1 = 1 3123
R/W 1 = 1 3124
R 1 = 1 1000
R 10 = 1,0°c 2112
R 10 = 1,0°c 2111
R 10 = 1,0°c 2113
R 10=1,0% 2121
R 10 = 1,0 g/Kg
R 10=1,0%
R 10 = 1,0 g/Kg
R 1=1%
R 1=1%
R 1=1%
R 1=1%
ELECTRICAL DATA
CONTROL VARIABLES
ECHELON
Settings and Readings
[On / Off] Unit
[Reset] Discharges the safety measures of the unit
[BMS] Activation of the Inoccupation mode [Off] occupation mode - [On] inoccupation mode
[Clock] [OFF] read hour & minute [ON] write hour & minute
[Alarm] General
[On/Off] Fan, Blower
[On/Off] Compressor, 1
[On/Off] Compressor, Heat pump, 1
[On/Off] Compressor, 2
[On/Off] Compressor, Heat pump, 2
[On/Off] Compressor, 3
[On/Off] Compressor, Heat pump, 3
[On/Off] Compressor, 4
[On/Off] Compressor, Heat pump, 4
[On/Off] Gas, Burner, 1
[On/Off] Gas, Burner, 2
[On/Off] Gas, Burner, High power, 1
[On/Off] Electrical heaters, 1
[On/Off] Electrical heaters, 2
[ BMS ] Activation of the control by a computer or an automat -
mode BMS is activated if this value is different from zero, This value is decreased every second
[Occupation][Room SP] Required maximum room temperature in °C.
Cooling set point
[Occupation][Room SP] Required minimum room temperature in °C.
Heating set point
[RoomSP]Requiredroomminimumfreshairratein%.
Middle of the dead zone
[Inoccupation][Room SP] Required maximum room temperature in °C.
Cooling set point
[Inoccupation][Room SP] Required minimum room temperature in °C.
Heating set point
[Humidity]DesiredMaximumrelativehumidityinRoom(in%).–
Dehumidicationsetpoint
[Humidity]DesiredMinimumrelativehumidityinRoom(in%).–
Humidicationsetpoint
[Clock] Hour
[Clock] Minute
[Clock] Day of the month
[Clock] Month
[Alarm] Code Error
[Temperature] Room
[Temperature] Outdoor
[Temperature] Supply
[Relative Humidity] Outdoor
[Absolute Humidity] Outdoor
[Relative Humidity] Room
[Absolute Humidity] Room
[%ofopening]Registeroffreshair
[%ofopening]Valvegas
[%ofopening]Electricalheaters(Triac)
[%ofopening]Hotwatercoil