Specifications
7 © Copyright 2004 - 2009 The Fire Company Pty Ltd. All rights reserved. V5 0709.
Clearances & Installation ENGLISH
Clearances &
Installation
The installation & clearances guidelines below are provided as a general overview only. Detailed installation
specifications are available for each individual model of the EcoSmart™ Fire range and should have been
referred to and taken into account prior to your purchase. To ensure the installation complies with our
Compulsory Installation & Clearance Requirements please contact The Fire Company Pty Ltd or one of its
representatives for a copy of the relevant specification to be sent to you.
The Around Burner is primarily intended for outdoor use. All other Burners are primarily intended for indoor
use, however when any Burner is used outdoors, it is important that the Burner be positioned in a large open
space ensuring that the nearest combustible (trees, branches, umbrellas, ceilings etc) are a minimum of
2000mm [78.74in] away in all weather conditions (for example, on windy days where there is movement in
branches, the clearance must still be met). When not in use it is recommended that you protect the model
from water damage or corrosion by covering. Burner Covers are available.
Clearances
INSERTING WITHIN A FIREBOX SETTING
The EcoSmart™ Burner can only be fitted into a firebox that has minimum clearances as outlined below.
Burner Kits Firebox Width
Metric mm
Imperial [in]
Firebox Depth
Metric mm
Imperial [in]
Overhead
Metric mm
Imperial [in]
Rear
Metric mm
Imperial [in]
Front
Metric mm
Imperial [in]
Burner One &
Burner Two
650
[25.6]
365
[14.4]
650
[25.6]
30
[1.2]
45
[1.8]
XL Burner
1100
[43.3]
500
[19.7]
500
[19.7]
40
[1.6]
50
[2.0]
Around Burner
650
[25.6]
365
[14.4]
650
[25.6]
30
[1.2]
45
[1.8]
Triple Burner
1200
[49.6]
500
[19.7]
750
[29.5]
40
[1.6]
65
[2.6]
Custom made fireboxes must:
- be made out of a non-combustible material such as stainless steel;
- be constructed to accommodate a Top Tray or “Twin Skin” (NOTE: Not applicable for the Around Burner);
- have built in spacers of 20mm [0.8in] on all sides to ensure that it does not sit directly against any
combustible materials and an air gap is incorporated for insulation around the box construction.
Burner One & Burner Two XL Burner
Around Burner
min
[25.6in]
650mm
min
[1.2in]
30mm
min
[1.8in]
45mm
min
[25.6in]
650mm
min
[14.4in]
365mm
min
[0.8in]
20mm
spacers
Triple Burner