Installation, Operation and Maintenance Manual Oil Fired Warm Air Furnaces HML-C (Up-Flow Model) HMLV-C (Up-Flow Model with ECM) ALL INSTALLATIONS MUST MEET ALL LOCAL, PROVINCIAL/STATE, AND FEDERAL CODES WHICH MAY DIFFER FROM THIS MANUAL ECR International Limited Read this complete manual before beginning installation.
TABLE OF CONTENTS 1. INTRODUCTION ................................................................................................................................. 3 2. HEAT LOSS ........................................................................................................................................ 3 3. LOCATION OF UNIT.......................................................................................................................... 3 4. AIR CONDITIONING APPLICATIONS .................
IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE should be centralized with respect to the supply and return air ductwork. A central location minimizes the trunk duct sizing. All models may be installed on combustible floors. 1. INTRODUCTION Please read these instructions completely and carefully before installing and operating the furnace. The minimum installation clearances are listed in Table 1.
installation, the dampers or air controlling means must prevent chilled air from entering the furnace. If the dampers are manually operated, there must be a means of control to prevent the operation of either system unless the dampers are in the full heat or full cool position. The air heated by the furnace shall not pass through a refrigeration unit unless the unit is specifically approved for such service.
regulator. The flue outlet pressure (measured between the furnace and draft regulator, or the oil burner mounting plate over-fired draft access port. fig. 2) should be set to -0.02 in. w.c. CHART 1 United Technologies 1158-120 (HML-C) Dip Switch Position Blower Delay Times 1 2 3 4 On Off Seconds Minutes Off Off 30 On Off 60 Off On 90 On On 120 Off Off 1 On Off 2 Off On 4 On On 6 9b. FAN TIMER BOARD AND LIMIT CONTROL (FIG. 5) (page 22) 8.
transformers may be powered from the electronic fan timer board where provisions have been made for connections, but should have their own controls. Do not use the direct drive motor connections as a power source, since there is a high risk of damaging the accessories by exposure to high voltage from the autogenerating windings of the direct drive motor. burner nozzle smaller than 0.65 U.S. Gallons Per Hour, install an additional 7 to 10 micron filter as close as possible to the oil burner. 14.
NOTE: Beckett AF Series Burner electrode specifications have been revised. They should be adjusted to be 5/16” above the nozzle centerline. lack block ends on the trunk ducts. These systems may require modification to provide some resistance to the airflow to prevent over-amping of the direct drive blower motor. Selecting a lower blower speed may correct this problem. Direct drive blower speeds are adjusted by changing the "hot" wires to the motor winding connections.
pipe and fittings. The barometric damper should open and close freely. 20. MAINTENANCE AND SERVICE Routine Maintenance By Home Owner All electrical connections should be checked to ensure tight connections. Safety controls such as the high limit controls should be tested for functionality. The fan control should be checked to ensure that the fan on and off delay function continues to start and stop the blower fan at the optimal settings.
After three or four minutes of burner operation, the limit control should turn the burner off. When the limit function test is complete, shut off electrical power to the furnace, replace the neutral wire to the blower fan motor, and then restore power. The blower fan will start up immediately. Once the temperature has dropped and the limit control has reset, the fan will operate until the fan off time is achieved. The oil burner will then resume operation and continue until the thermostat is satisfied.
Appendix A- HML-C AND HMLV-C HML-C and HMLV-C furnaces may be used with the following oil burners. Please note: The Beckett AF, and Riello 40F oil burners are for applications using indoor air for combustion only. For sidewall venting applications utilizing outdoor air for combustion, use the Beckett AFII or the Riello 40BF (Balanced Flue) oil burners only.
Table A-3 Riello 40F Series Oil Burner Set-Up Riello 40F Series Oil Burners (For use with chimney vented units) Furnace Model HML-60CRF HMLV-60CRF HML-80CRF HMLV-80CRF HML-90CRF HMLV-90CRF Output BTU/Hr Burner Model Nozzle Pump Pressure Flow Rate Air Gate Turbulator Setting 59,000 40F3 0.50 / 60°W 105 PSIG 0.50 USGPH 2.6 1.0 75,000 40F3 0.60 / 60°W 115 PSIG 0.65 USGPH 2.6 1.5 86,000 40F3 0.65 / 60°W 135 PSIG 0.75 USGPH 3.6 2.
A.2 BURNER ELECTRODES NOTE: USE OF THE INLET AIR SHUT-OFF COULD CAUSE POST COMBUSTION NOZZLE DRIP. Adjustment of the electrode tips with respect to each other, the nozzle, and to the rest of the burner is very important to ensure smooth start-ups and to permit efficient combustion. A.
Table A-6 Direct Drive Blower Set-Up PSC Motor Blower Set-Up Furnace Model Blower 0.20 in. w.c. Cooling Capacity 0.50 in. w.c.
Table A-9 General Dimensions (Inches) Cabinet Furnace Model HML-C HMLV-C Plenum Openings Width Depth Height Supply 22 30-3/4 49-5/8 20½ x 20 Return Side Bottom 14 x 22 14 x 22 14 Filter Shipping Weight Flue Diameter Type Size 5 Permanent 16 x 25 x 1 (LB.
Table A-10 ECM Blower Set-Up (HMLV-C) DIP SWITCH ADJUSTMENT CHART FOR INPUT 0.50 USGPH TO 0.85 USGPH SW1 - HEAT DIP Switch Position 1 2 OFF OFF ON OFF OFF ON ON ON SW3 - ADJUST DIP Switch Position 1 2 OFF OFF ON OFF OFF ON ON ON SW2 - COOL POS. A B C D INPUT USGPH 0.65 0.85 0.75 0.50 DIP Switch Position 1 2 OFF OFF ON OFF OFF ON ON ON POS. A B C D AC Size (TON) 3 2.5 2 1.5 SW4 - DELAY POS. A B C D CFM 0% (+)15% (-)15% N/A DIP Switch Position 1 2 OFF OFF ON OFF OFF ON ON ON POS.
Chimney Vent Burner Wiring Diagram HML-C HMLV-C APPENDIX B: WIRING DIAGRAMS LEGEND/legende 120 V 24 V FACTORY WIRING filage a l'usine 120 V 24 V FIELD WIRING filage au champs INDOOR BLOWER ventilateur principale MOTOR moteur L C ML H MHI L1 530SE BL COM 24V BK YL WH CAP BL V VALVE/ soupappe 3 4 5 HUM 2 N EAC 2 COOL 1 1 HEAT 3 6 7 VI C YL GR 3 3 WH 4 WH AL 1008 11 BR BL 3 1 2 4 1 3T (T1) 2 BURNER MOLEX CONNECTOR/ connecteur molex du brûleur 1 2 BECKETT OIL PRI
Direct Vent Burner Wiring Diagram HML-C HMLV-C LEGEND/legende 120 V 24 V FACTORY WIRING filage a l'usine 120 V 24 V FIELD WIRING filage au champs 3 INDOOR BLOWER ventilateur principale BR BR MOTOR moteur L C ML H MHI GROUND/Terre TERMINAL PROVIDED/ point de raccord fourni BK WH 120V 1 2 3 24V COM 24V VI YL BL F C V NC OR BR BK WH WH CAP 3 4 5 N 2 6 VI X HUM 2 COOL 1 1 HEAT 3 EAC VALVE/ soupappe YL BURNER V VI 7 C RD RD 3 11 WH 12 RD WH 4 2 1 4 2 1 5
the heat anticipator. Set the heat anticipator to the amperage measured. OPERATION OF OIL BURNER Once the furnace flue pipe, electrical and oil line connections have been made, use the following instructions to set the burner: NOTE: THE FURNACE SHOULD BE RUN THROUGH AT LEAST THREE FULL CYCLES BEFORE LEAVING THE INSTALLATION, TO ENSURE THAT ALL CONTROLS ARE OPERATING PROPERLY AND AS EXPECTED. Shut off the electrical power to the furnace. Install an oil pressure gauge to the pressure port on the oil pump.
APPENDIX C OIL PRIMARY CONTROL DETAILED SEQUENCE OF OPERATION Power is applied to unit. The oil primary control completes a self-diagnostic procedure. If no light or flame is present, and unit passes its self-diagnostic procedure, the control enters into the idle mode. Thermostat calls for heat: A) Safety check is made for flame (4 second delay). 1) If flame is not present, the oil primary control will apply power to the burner motor and igniter.
FIGURE 4: UNITED TECHNOLOGIES 1158-120 FAN TIMER BOARD (HML-C) FIGURE 5: UNITED TECHNOLOGIES 1168-1 ECM TAP BOARD (HMLV-C) 20 30173 Rev B 4/29/2008
IDLE STATE THERMOSTAT CALLS FOR HEAT SAFETY CHECK FOR FLAME (5 SEC.) OIL PRIMARY CONTROL SEQUENCE of OPERATION REMAINS IN IDLE STATE NO FLAME FLAME BURNER MOTOR & IGNITOR START 10 SEC. SAFETY CHECK FOR FLAME (5 SEC.
Table C-1: 1158-120 ELECTRONIC FAN TIMER BOARD (EFT) DETAILED SEQUENCE OF OPERATION Mode Action Thermostat calls for heat. ("W" terminal is energized). HEAT Thermostat ends call for heat. ("W" terminal is de-energized). Burner fails to light. Established flame fails. COOL FAN Thermostat begins call for cool. (G and Y terminals are energized). Thermostat ends call for cool. (G and Y terminals are deenergized). Thermostat begins call for fan. (G terminal is energized). Thermostat ends call for fan.
TROUBLESHOOTING OIL PRIMARY CONTROL LED DIAGNOSTIC LIGHT IMPORTANT: Due to the potential hazard of line voltage, only a trained, experienced service technician should perform the troubleshooting procedure. The LED diagnostic light has several functions. It indicates the state or mode in which the oil burner is operating. It will also indicate fault conditions, and help determine cad cell resistance while the burner is operating.
PRELIMINARY CHECKS: Make sure that limit switches are closed and those contacts are clean. ELECTRICAL SHOCK HAZARD. TROUBLESHOOTING IS DONE WITH THE SYSTEM POWERED. BE CAREFUL TO OBSERVE ALL NECESSARY PRECAUTIONS TO PREVENT ELECTRICAL SHOCK OR EQUIPMENT DAMAGE. Check for line voltage power on the oil primary control black and white lead wires. Refer to Table C-4 or C-5 for further troubleshooting information.
Table C-3: Oil Primary Control Troubleshooting continued from previous page Procedure 4. Shield cad cell from external light. 5. Jumper thermostat (T -T) terminals on oil primary control IMPORTANT First remove one thermostat lead wire. Status Indicator light turns off. Corrective Action Eliminate external light source or permanently shield cad cell. Replace cad cell with new cad cell and recheck. If indicator light does not turn off, remove cad cell lead wires from oil primary control and recheck.
Table C-3: Oil Primary Control Troubleshooting continued. Procedure Status Corrective Action Indicator light is on. Remount control onto burner housing. Go to step 6. 10. Check cad cell. Disconnect line voltage power and open line switch. Remove existing cad cell and replace with new cad cell. Disconnect all wires from thermostat terminals to ensure Indicator light is off. Go to step 11. that there is no call for heat. Reconnect line voltage power and close line switch.
Table C-4: System and General Troubleshooting continued Problem Furnace will not start. Possible Cause Photo Cell wiring shorted or room light leaking into photo cell compartment Open safety switch. No fuel oil. Clogged nozzle. Furnace will not start without first pushing oil primary control reset button. (Happens on frequent basis) Clogged oil filter. Low oil pump pressure. Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective. Defective burner motor.
Table C-4: System and General Troubleshooting continued Problem Possible Cause System temperature rise too high. Poor “fan off” delay timing selection, (fan stops too soon). Excessive fuel oil consumption. Fuel oil leak. Check fuel oil line for leaks. Repair or replace if necessary. Stack temperature too high. Check stack temperature. Stack temperatures will normally range from 350° to 450°F. Check draft regulator. Draft should be set to -0.02 in. w.c.
Table C-4: System and General Troubleshooting continued Problem Supply air temperature too hot. Supply air temperature too cool. Supply air temperature too cool during first moments of furnace cycle. Possible Cause Airflow blocked or dirty air filter. Insufficient airflow. Excess airflow. Excessive duct losses. Fan control "fan on" setting too low. Excessive duct losses. Remedy Clean or replace air filter. Check all dampers. Open closed dampers including registers in unused rooms.
HOMEOWNER’S REFERENCE TABLE Model No. Serial No. Date Installed Contractor Contact Address Postal Code Telephone No. After Hours No. FUEL SUPPLIER Fuel Oil Supplier Contact Telephone No. After Hours No. IF DIFFERENT FROM INSTALLATION CONTRACTOR: Service Tech. Telephone No. After Hours No.
PARTS LISTING: HIGHBOY MODEL: HML-80C AND HMLV-80C Ref. No. Description Part No.
PARTS LISTING: HIGHBOY MODEL: HML-80C HMLV-80C Ref. No. Description Part No.
30173 Rev B 4/29/2008
30173 Rev B 4/29/2008
30173 Rev B 4/29/2008
NOTES: 6800 Base Line, Wallaceburg, Ontario, N8A 5E5, Can. Tel: (519) 627-0791 Fax: (519) 627-4719 2201 Dwyer Avenue, Utica, New York, 13504, USA. Tel: (315) 797-1310 Fax: (315) 724-9319 85 Middle Road, Dunkirk, New York, 14048, USA Tel: (716) 366-5500 Fax: (716) 366-1209 www.ecrinternational.