5. Locating the Unit - [See Figure 1 and Table 1]
Locate furnace so ue connection to chimney is short,
direct and consists of as few elbows as possible.
Centralize furnace location with respect to supply and
return air ductwork. Central location minimizes trunk
duct sizing.
All models may be installed on combustible oors.
6. Furnace Used In Conjunction With Air
Conditioning
Install furnace in parallel with or upstream from
evaporator coil to avoid condensation in heat
exchanger.
When installed in parallel, prevent chilled air from
entering furnace by use of dampers or air controlling.
Manually operated dampers must have a control to
prevent operation of either system unless dampers
are in full heat or full cool position.
Air heated by the furnace shall not pass through
evaporator coil unless coil is speci cally approved for
such service.
Check and adjust blower speed to compensate for
pressure drop caused by evaporator coil.
Table 1: Minimum Installation Clearances
Location
Clearance to Combustibles
HML and HMLV
Up ow
Top 1" (26 mm)
Bottom 0"
S/A Plenum 1" (26 mm)
Rear 1" (26 mm)
Sides 1" (26 mm)
Front 1"** (26 mm)
Flue Pipe 9"* (229 mm)
Enclosure Closet
*18 in. (458 mm) USA
** 24 in. (610 mm) Service Clearance
Heat Exchanger Support Screws
Remove heat exchanger support screws before nal
placement of the furnace.
Preferable if furnace rear panel is inaccessible after
installation.
Screws must be removed if heat exchanger is to be
removed from the cabinet.
Figure 1 - Heat Exchanger Support Screw Location