RK0YG302 © Danfoss 04/2007 101
EKC 414C1
Inject ON function
The expansion valve closes when the signal at the 230 V input is
removed. In this way it is ensured that the expansion valve will not
charge the evaporator when the compressor has stopped.
In stead of wiring the function can be made via data communica-
tion.
Digital input
A digital input can be dened for one of the following
applications:
Door alarm
Defrost start
Night operation
Start/stop of regulation
Joint defrost start/stop with a master/slave function
EKC 414C1
Application
The controller is a complete control unit for refrigeration
appliances with integrated refrigeration-technical functions
capable of replacing a setup of thermostats and timers.
The relays are used for operating:
- Compressor
- Fan
- Defrost
- Rail heat
- Alarm or light function
The controller should only be used in installations where the placing
of the S1 sensor, and hence the signal reliability, has been checked in
advance.
Operation
The controller comes without operating buttons on the front
panel, and it will require no operation once it has been set and
started up.
When the controller is operated, it can be done in one of the
following ways:
• Connection of an external display with operating buttons
- The display will currently show measurements and settings in
the menu system
- In case of malfunction the relevant error code will be shown on
the display
- Four light-emitting diodes will show the system’s actual
function:
› refrigeration
› power for the AKV valve
› defrost
› fan operating
› when there is an alarm the three LED’s will ash
• Data communication
The controller can be hooked up with other products in the
series of ADAP-KOOL®
refrigeration controls. The operation,
monitoring and data collection can then be performed from a
PC – either on site or at a service company.
Customer display
If the temperature in the appliance is to be visible to, say,
customers, a display can be mounted.