Specifications
104 RK0YG302 © Danfoss 05/2007
Data
EKC 414C1
Continued from previous page
Para-
meter
Min. Max.
Fac.
setting
AKV-ON denition
When the ON input is cut out refrigeration is
stopped.
Here you dene how the fan relay and the
alarm function are to act:
1 = Fan relay = ON, alarm monitoring active
2 = Fan relay = OFF, alarm monitoring active
3 = Fan relay = OFF, no alarm monitoring
4 = Fan relay = ON, no alarm monitoring
5 to 8 = as 1 to 4, but without connection to
terminal 40-41.
o29 1 8 6
Function for relay on terminal 29-31
1=Alarm relay. 2=Light relay
o36 1 2 1
Rail heat during day operation
Setting of ON period in % of time
o41
0% 100% 100
Rail heat during night operation
Setting of ON period in % of time
o42 0% 100% 100
Rail heat setting
Time period for aggregate ON/OFF time
o43 6 min.
60
min.
10
Service
The following readouts can be performed via the belonging parameter
Defrost sensor S5 S
def
u09 °C
Status on DI-input u10
Defrost time u11 min.
Air temperature S3 (S
in
) u12 °C
Status on night operation (on or o) u13
Status on ON-input u14
Status on DO-output u15
Air temperature S4 (S
out
) u16 °C
Thermostat temperature u17 °C
Thermostat cut-in time u18 min.
Temperature at S1 u19
°C
Temperature at S2 u20 °C
Superheat u21 K
Superheat reference u22 K
AKV valve’s actual opening degree u23 %
Status on rail heat u41
Weighted temperature for S3/S4 (CPT-temp.) u56 °C
Supply
voltage
230 V +10/-15%, 50/60 Hz, 5 VA
Sensors
Pt 1000 ohm for refrigerant temperatures
Pt 1000 ohm or PTC (R25 = 1000 ohm) for air
temperatures
Controller
sensor system
Measuring range -60 to +50°C
Accuracy
±0.5°C
for sensor temperature =
-35 to +50°C
Display/ opera-
tion
The controller has no display or operating buttons on
front panel.
Operation takes place via a separate, connected display
or via data communication
It is possible to connect two displays with 0.1% reading
accuracy in the measuring range:
EKA 163, LED, three digits
EKA 164, LED, three digits, + operating buttons
1 digital input
If a contact function is connected, ir can be used for
door alarm, defrost start, night operation, door function
or start/stop of the regulation
If other EKC 414C1 units are connected, coordinated
defrost can be performed via cable connections
1 digital
output
May in conjunction with the digital input be used for
coordinated defrost via cable connections
230 V input
0 V: regulation stopped. The compressor relay, the de-
frost relay, the fan relay and rail heat relay are cut out.
230 V a.c.: regulation
Real time clock
For start of defrost. Can be mounted if data communi-
cation not is used.
Electric
connection
Via separate plug
AKV
connection
Max. 1 AKV or AKVA. Coil = 230 V d.c.
Relays
Compressor relay
SPST NO, I
max.
= 6 A ohmic/ 3 A
a.c. 15* inductive
Defrost relay
SPST NO, I
max.
= 6 A ohmic/3 A
a.c. 15* inductive
Fan motor relay
SPST NO, I
max.
= 6 A ohmic/3 A
a.c. 15* inductive
Rail heat relay
SPST NO, I
max.
= 6 A ohmic/3 A
a.c. 15* inductive
Relay for alarm
function or for light
function
SPDT, I
max.
= 6 A ohmic/3 A a.c.
15* inductive
Environments
0 to +55°C, during operations
-40 to +70°C, during transport
20 - 80% Rh, not condensed
No shock inuence/vibrations
Mounting On DIN rail or on wall
Enclosure IP 20
Weight 0.4 kg
Approvals
EU Low Voltage Directive and EMC demands re CE-
marking complied with.
LVD-tested acc. to EN 60730-1 and EN 60730-2-9
EMC-tested acc. to EN 50081-1 and EN 50082-2