Specifications
124 RK0YG302 © Danfoss 05/2007
Menu survey
SW =1.2x
EKC 312
Function
Para-
meter
Min. Max.
Fac.
Set-
tings
Normal display
Shows the actual superheat/ valve's opening
degree/ temperature
Dene view in o17
-K
If you wish to see the expansion valve’s actual
opening degree, give the lower button a brief
push (1s). Dene view in o17
-%
Reference
Units (0=°C+bar /1=°F+psig)
r05 0 1 0
Start/stop of refrigeration r12 OFF On 1
Regulating parameters
P: Amplication factor Kp n04 0.5 20 3
I: Integration time T n05 30 s 600 s 120
Max. value of superheat reference n09 2 K 30 K 10
Min. value of superheat reference n10 1 K 12 K 4
MOP n11 0.0 bar 20 bar 20
Amplication factor for superheat
Changes should only be made by trained sta
n20 0.0 10.0 0,4
Value of min. superheat reference for loads
under 10%
n22 1 K 15 K 2
”n37” and ”n38” are adapted to valve type ETS 50
and should only be changed through the use of
another valve.
Number of steps from 0-100% opening degree
(x10)
(ETS 50= 263. ETS 100 = 353)
n37
000
stp*
5000
stp *
263
Number of steps per second n38
10
stp/s
300
stp/s
250
Integration time for inner loop (TnT0) n44 10 s 120 s 30
Miscellaneous
Controller’s address o03* 1 60
ON/OFF switch (service-pin message) o04* - -
Set supply voltage frequency o12 50 Hz 60 Hz 50
Select display for ”normal picture”
1: Superheat
2: Valve’s opening degree
3: Air temperature
o17
131
Manual control of outputs:
OFF: no manual control
3: Alarm relay activated (cut out)
At settings 3, ”o45” will be active
o18
o 3 0
Working range for pressure transmitter – min.
value
o20 -1 bar 60 bar -1.0
Working range for pressure transmitter – max.
value
o21 -1 bar
60 bar 12
Refrigerant setting
1=R12. 2=R22. 3=R134a. 4=R502. 5=R717.
6=R13. 7=R13b1. 8=R23. 9=R500. 10=R503.
11=R114. 12=R142b. 13=User dened.
14=R32. 15=R227. 16=R401A. 17=R507.
18=R402A. 19=R404A. 20=R407C. 21=R407A.
22=R407B. 23=R410A. 24=R170. 25=R290.
26=R600. 27=R600a. 28=R744. 29=R1270.
o30 0 29 0
Manual control of the valve’s opening degree.
The function can only be operated if ”o18” has
been set.
o45 0 % 100 % 0
Selection of loop ctrl:
1=Normal
2 = double loop
o56 1 2 1
Service
Read status of input DI u10 on/o
Temperature at S2 sensor u20 °C
Superheat u21 K
Superheat reference u22 K
Read AKV valve’s opening degree u24 %
Read evaporating pressure u25 bar
Read evaporating temperature u26 °C
Temperature at S4 sensor u27 °C
Read signal at pressure transmitter input u29 mA