Specifications

126 RK0YG302 © Danfoss 05/2007
EKC 315A
Water chiller application Air cooler application
EKC 315A
Application
The controller and valve can be used where there are require-
ments to accurate control of superheat and temperature in con-
nection with refrigeration.
E.g.:
Cold store (air coolers)
Processing plant (water chillers)
• A/C plant
Advantages
The evaporator is charged optimally – even when there are
great variations of load and suction pressure
Energy savings – the adaptive regulation of the refrigerant injec-
tion ensures optimum utilisation of the evaporator and hence a
high suction pressure
Exact temperature control – the combination of adaptive
evaporator and temperature control ensures great temperature
accuracy for the media
The superheating is regulated to the lowest possible value at
the same time as the media temperature is controlled by the
thermostat function
Functions
Regulation of superheat
• Temperature control
• MOP function
ON/OFF input for start/stop of regulation
Input signal that can displace the superheat reference or the
temperature reference
Alarm if the set alarm limits are exceeded
Relay output for solenoid valve
• PID regulation
Output signal following the temperature showing in the display
System
The superheat in the evaporator is controlled by one pressure
transmitter P and one temperature sensor S2.
The valve can be one of the following types:
• ICM
• AKV (AKVA)
ICM is an electronically, directly run engine valve, controlled by an
ICAD type actuator. It is used with a solenoid valve in the liquid
line.
AKV is a pulsating valve.
Where the AKV valve is used it also functions as solenoid valve.
Temperature control is performed based on a signal from
temperature sensor S3 which is placed in the air current before
the evaporator. Temperature control is in the shape of an ON/OFF
thermostat that shuts o the liquid ow in the liquid line.