Specifications

128 RK0YG302 © Danfoss 05/2007
Menu survey
SW =1.3x
EKC 315A
Function
Para-
meter
Min. Max.
Factory
setting
Normal display
Shows the actual superheat/ valve's opening
degree/ temperature
Dene view in o17
-K
Temperature, superheating, or the temp. reference
is displayed if the bottom button is pressed briey.
Dene view in o17
-%
Reference
Set the requirede set point - -60°C 50°C 10
Dierential r01 0.1 K 20 K 2.0
Units (0=°C+bar /1=°F+psig)
r05 0 1 0
External contribution to the reference r06 -50 K 50 K 0
Correction of signal from S2 r09 -10.0 K 10.0 K 0.0
Correction of signal from S3 r10 -10.0 K 10.0 K 0.0
Start/stop of refrigeration r12 OFF On 1
Dene thermostat function
(0= no thermostat function, 1=On/o thermostat)
r14
010
Alarm
Upper deviation (above the temperature setting) A01 3.0 K 20 K 5.0
Lower deviation (below the temperature setting) A02 1 K 10 K 3.0
Alarm’s time delay A03 0 min.
90
min.
30
Regulating parameters
P: Amplication factor Kp n04 0.5 20 3.0
I: Integration time T n05 30 s 600 s 120
D: Dierentiation time Td (0 = o) n06 0 s 90 s 0
Max. value of superheat reference n09 2 K 50 K 6
Min. value of superheat reference n10 1 K 12 K 4
MOP (max = o) n11 0.0 bar 60 bar 60
Period time (only when AKV/A valve is used) n13 3 s 10 s 6
Stability factor for superheat control.
Changes should only be made by trained sta
n18
0105
Damping of amplication around reference value
Changes should only be made by trained sta
n19
0.2 1.0 0.3
Amplication factor for superheat
Changes should only be made by trained sta
n20 0.0 10.0 0.4
Denition of superheat control
1=MSS, 2=LOADAP
n21
121
Value of min. superheat reference for loads under
10%
n22 1 15 2
Standby temperature when valve closed (TQ valve
only)
Changes should only be made by trained sta
n26 0 K 20 K 0
Standby temperature when valve open (TQ valve
only)
Changes should only be made by trained sta
n27 -15 K 70 K 20
Max. opening degree
Changes should only be made by trained sta
n32 0 100 100
Min. opening degree
Changes should only be made by trained sta
n33 0 100 0
Miscellaneous
Controller’s address o03* 0 119 -
ON/OFF switch (service-pin message) o04* - - -
Dene valve and output signal:
0: O
1: TQ. AO: 0-20 mA
2: TQ. AO: 4-20 mA
3: AKV, AO: 0-20 m
4: AKV, AO: 4-20 mA
5: AKV, AO: EKC 347-SLAVE
6: ICM, AO: 0-20 mA/ICM OD%
7: ICM, AO: 4-20 mA/ICM OD%
o09 0 7 0
Dene input signal on the analoge input AIA:
0: no signal,
1: Temperature setpoint. 0-20 mA
2: Temperature setpoint. 4-20 mA
3: Displacement of superheat reference. 0-20 mA
4: Displacement of superheat reference. 4-20 mA
o10
040
Set supply voltage frequency o12 50 Hz 60 Hz 0
Select display for ”normal picture”
(Display the item indicated in parenthesis by
briey pressing the bottom button)
1: Superheat (Temperature)
2: Valves opening degree (Superheat)
3: Air temperature (Temperature reference)
o17
131
Manual control of outputs:
OFF: no manual control
1: Relay for solenoid valve: select ON
2: AKV/A output: select ON
3: Alarm relay activated (cut out)
o18
o 3 O
Working range for pressure transmitter – min.
value
o20 -1 bar 60 bar -1.0
Working range for pressure transmitter – max.
value
o21 -1 bar
60 bar 12
(Setting for the function o09, only AKV and TQ)
Set the temperature value or opening degree
where the output signal must be minimum (0 or
4 mA)
o27 -70°C 160°C -35
(Setting for the function o09, only AKV and TQ)
Set the temperature value or opening degree
where the output signal must be maximum (20
mA)
o28 -70°C 160°C 15
Refrigerant setting
1=R12. 2=R22. 3=R134a. 4=R502. 5=R717.
6=R13. 7=R13b1. 8=R23. 9=R500. 10=R503.
11=R114. 12=R142b. 13=User dened. 14=R32.
15=R227. 16=R401A. 17=R507. 18=R402A.
19=R404A. 20=R407C. 21=R407A. 22=R407B.
23=R410A. 24=R170. 25=R290. 26=R600.
27=R600a. 28=R744. 29=R1270.
o30 0 29 0
Service
TQ valve's actuator temperature u04 °C
Reference of the valve's actuator temperature u05 °C
Analog input AIA (18-19)
u06 mA
Analog output AO (2-5) u08 mA
Read status of input DI u10 on/o
Thermostat cut-in time u18 min.
Temperature at S2 sensor u20 °C
Superheat u21 K
Superheat reference u22 K
Read AKV valve’s opening degree u24 %
Read evaporating pressure u25 bar
Read evaporating temperature u26 °C
Temperature at S3 sensor u27 °C
Temperature reference u28 °C
Read signal at pressure transmitter input u29 mA