Specifications
RK0YG302 © Danfoss 04/2007 129
Data
Ordering
Type Function Code no.
EKC 315A Superheat controller 084B7086
EKA 175
Data communication module
(accessories), (RS 485 modul)
084B7093
EKA 174
Data communication module
(accessories), (RS 485 module)
with galvanic separation
084B7124
Additional information!
Manual: RS8CS
EKC 315A
The installation of data communications must comply with the require-
ments described in literature sheet no. RC8AC
Supply voltage
24 V a.c. +/-15% 50/60 Hz, (80 VA)
(the supply voltage is galvanically separated
from the input and output signals)
Power consumption Controller
AKV coil
5 VA
55 VA
Input signal
Current signal 4-20 mA or 0-20 mA
Pressure transmitter 4-20 mA from AKS 33
Digital input from external contact function
Sensor input 2 pcs. Pt 1000 ohm
Output signal
Current signal 4-20 mA or 0-20 mA
Load Max. 200 ohm
Relay output 1 pcs. SPST
AC-1: 4 A (ohmic)
AC-15: 3 A (inductive)
Alarm relay 1 pcs. SPST
ICAD
ICAD mounted on
ICM
Current signal
4-20 mA or 0-20 mA
Data communication
Possible to connect a data communication
module
Environments
-10 to 55°C, during operations
-40 to +70°C, during transport
20 - 80% Rh, not condensed
No shock inuence/vibrations
Enclosure IP 20
Weight 300 g
Mounting DIN rail
Display LED, 3 digits
Terminals max. 2.5 mm
2
multicore
Approvals
EU Low Voltage Directive and EMC demands re
CE-marking complied with.
LVD-tested acc. to EN 60730-1 and EN 60730-
2-9
EMC-tested acc. to EN50081-1 and EN 50082-2
Data communication