Specifications
132 RK0YG302 © Danfoss 05/2007
Menu survey
SW =1.2x
EKC 316A
Function
Pa-
ram-
eter
Min. Max.
Fac.
sett.
Normal display
Shows the actual superheat/ valve's opening
degree/ temperature
Dene view in o17
-K
If you wish to see the expansion valve’s actual
opening degree, give the lower button a brief
push (1s). Dene view in o17
-%
Reference
Set the required set point for the thermostat - * -60°C 50°C 3.0
Dierential r01 * 0.1 K 20.0 K 2.0
Units (0=°C+bar /1=°F+psig)
r05 0 1 0
External contribution to the reference r06 -50 K 50 K 0..0
Correction of signal from S2 r09 -10.0 K 10.0 K 0.0
Correction of signal from S3 r10 -10.0 K 10.0 K 0.0
Start/stop of refrigeration r12 OFF On On
Dene thermostat function
(0= no thermostat function, 1=On/o thermostat)
r14
01 0
Alarm
Upper deviation (above the temperature setting) A01 * 3 K 20 K 5
Lower deviation (below the temperature setting) A02 * 1 K 10 K 3
Alarm’s time delay A03 * 0 min. 90 min. 30
Battery monitoring A34 O On O
Regulating parameters
P: Amplication factor Kp n04 0.5 20 3.0
I: Integration time T n05 30 s 600 s 120
D: Dierentiation time Td (0 = o) n06 0 s 90 s 0
Max. value of superheat reference n09 2 K 30 K 10
Min. value of superheat reference n10 1 K 12 K 4
MOP (max = o) n11 0.0 bar 20 bar 20
Signal reliability during start-up. Safety time
period.
Should only be changed by trained sta
n15
0 s 90 s 0
Signal reliability during start-up – Opening
degree’s start value. Should only be changed by
trained sta.
n17
0 100 0
Stability factor for superheat control.
Changes should only be made by trained sta
n18
0105
Damping of amplication around reference
value
Changes should only be made by trained sta
n19
0.2 1.0 0.3
Amplication factor for superheat
Changes should only be made by trained sta
n20 0.0 10.0 0.4
Denition of superheat control
1=MSS, 2=LOADAP
n21
12 1
Value of min. superheat reference for loads
under 10%
n22 1 K 15 K 2
Max. opening degree
Changes should only be made by trained sta
n32 0 % 100 % 100
”n37” to ”n42” are adapted to valve type ETS 50
and should only be changed through the use of
another valve.
Number of steps from 0-100% opening degree
(x10)
(ETS 50 = 263. ETS 100 = 353)
n37
000
stp**
5000
stp **
263
Number of steps per second n38
10
stp/s
300
stp/s
250
Compensation of spindle play at the valve’s
closing point
n39 0 stp 100 stp 50
Compensation of spindle play in the control
range
n40 0 stp 100 stp 100
Valve status when power supply interrupted:
1 = NC, 2 = NO (special application)
n41
12 1
Compensation of spindle play at the closing
point must take place: 1=when the valve opens,
2=when the valve closes
n42 1 2 stp 1
Attenuation factor for inner loop n43 0,1 1 0.4
Integration time for inner loop (TnT0) n44 10 s 120 s 30
Safety value for lower temperature dierence
for inner loop
n45 1 K 20 K 3.0
Miscellaneous
Controller’s address o03*** 0 119 0
ON/OFF switch (service-pin message) o04*** - - -
Dene input signal on the analoge input AIA:
0: no signal,
1: Temperature setpoint. 0-20 mA
2: Temperature setpoint. 4-20 mA
3: Displacement of superheat reference. 0-20 mA
4: Displacement of superheat reference. 4-20 mA
5: Forced control of valve's max. opening degree.
0-20 mA
6: Forced control of valve´s max. opening degree
4-20 mA
o10
06 0
Set supply voltage frequency o12 50 Hz 60 Hz 50
Select display for ”normal picture”
1: Superheat
2: Valve’s opening degree
3: Air temperature
o17
13 1
Manual control of outputs:
OFF: no manual control
1: Relay for solenoid valve: select ON
2: Relay for solenoid valve: select OFF
3: Alarm relay activated (cut out)
4: Forced control of valve's opening degree.
0-20 mA
5: Forced control of valve´s opening degree
4-20 mA
At settings 1-3, ”o45” will be active
o18 o 5 0
Working range for pressure transmitter – min.
value
o20 -1 bar 60 bar -1.0
Working range for pressure transmitter – max.
value
o21 -1 bar
60 bar 12.0
Refrigerant setting
1=R12. 2=R22. 3=R134a. 4=R502. 5=R717.
6=R13. 7=R13b1. 8=R23. 9=R500. 10=R503.
11=R114. 12=R142b. 13=User dened. 14=R32.
15=R227. 16=R401A. 17=R507. 18=R402A.
19=R404A. 20=R407C. 21=R407A. 22=R407B.
23=R410A. 24=R170. 25=R290. 26=R600.
27=R600a. 28=R744. 29=R1270.
o30 0 29 0
Manual control of the valve’s opening degree.
The function can only be operated if ”o18” has
been set.
o45 0 % 100 % 0
Selection of control mode:
1=Normal
2 = With inner loop (T0)
3 = With inner loop (S media temperature less T0)
o56 1 3 1
Service
Analog input AIA (16-17)
u06 mA
Read status of input DI u10 on/o
Thermostat cut-in time u18 min.
Temperature at S2 sensor u20 °C
Superheat u21 K
Superheat reference u22 K
Read AKV valve’s opening degree u24 %
Read evaporating pressure u25 bar
Read evaporating temperature u26 °C
Temperature at S3 sensor u27 °C
Temperature reference u28 °C
Read signal at pressure transmitter input u29 mA
*) Used only when thermostat function (r14 = 1) is selected.
**) The display on the controller can show 3 digits only, but the setting value has
4 digits. Only the 3 most important will be shown. It means f.ex. . 250 will give a
setting of 2500.
***) This setting will only be possible if a data communication module has been
installed in the controller.
Conguration settings available only when regulation is stopped.