Specifications
RK0YG302 © Danfoss 04/2007 137
Data
Ordering
Additional information!
Manual: RS8AX
Supply voltage
24 V a.c. +/-15% 50/60 Hz, 60 VA
(the supply voltage is galvanically separated
from the input and output signals. Input/output
are not individual galvanic isolated)
Power consumption
Controller
20 W coil for AKV
5 VA
55 VA
Input signal
Level signal 4-20 mA or 0-10 V
Reference displace-
ment
4-20 mA, 0-20 mA,
2-10 V or 0-10 V
ICM valve feedback
signal
From ICAD 0/4-20 mA
Contact function start/stop of regulation
Relay output 2 pcs. SPST
AC-1: 4 A (ohmic)
AC-15: 3 A (inductive)
Alarm relay 1 pcs. SPST
Current output
0-20 mA or 4-20 mA
Max. load: 500 ohm
Valve connection
ICM - via current output
AKV/A- via 24 a.c. Pulse-Width Modulating
output
Data communication
Possible to connect a data communication
module
Environments
-10 - 55°C, during operation
-40 - 70°C, during transport
20 - 80% Rh, not condensed
No shock inuence/vibrations
Enclosure IP 20
Weight 300 g
Mounting DIN rail
Display LED, 3-digits
Terminals max. 2.5 mm
2
multicore
Approvals
EU Low Voltage Directive and EMC demands re
CE-marking complied with.
LVD-tested acc. to EN 60730-1 and EN 60730-2-9
EMC-tested acc. to EN50081-1 and EN 50082-2
Type Function Code No.
EKC 347 Liquid level controller 084B7067
EKA 174
Data communication module
(accessories), (RS 485 module)
with galvanic separation
084B7124
Data communication
AKV/AKVA coil always 24 V a.c. max. 20 W.
May also be a relay with coil 24 V a.c.
EKC 347
The installation of data communications must comply with the require-
ments described in literature sheet no. RC8AC