Specifications

162 RK0YG302 © Danfoss 05/2007
AKV 10, AKV 15, AKV 20
Application
AKV are electrically operated expansion valves designed for
refrigerating plant.
The AKV valves can be used for HCFC-, HFC and R744-refrigerants.
The AKV valves are normally controlled by a controller from
Danfoss range of ADAP- KOOL® controllers.
Advantages
• The valve requires no adjustment
• Wide regulation range
• Replaceable orice assembly
• Both expansion valve and solenoid valve.
Function
The AKV valves are supplied as a component programme, as fol-
lows:
• Separate valve
Separate coil with terminal box or cable
Spare parts in the form upper part, orice and lter
The individual capacities are indicated with a number forming
part of the type designation. The number represents the size of
the orice of the valve in question. A valve with orice 3 will for
example be designated AKV 10-3.
The orice assembly is replaceable.
Approvals
DEMKO, Denmark
SETI, Finland
SEV, Switzerland
S UL listed (separate code. nos.)
A CSA certied (separate code. nos.)
Valve type AKV 10 AKV 15 AKV 20
Tolerance of coil
voltage
+10/–15%
Enclosure acc. to
IEC 529
Max. IP 67
Working principle PBM (Pulse-width modulation)
Recommend period
of time
6 seconds
Capacity (R22) 1 to 16 kW 25 to 100 kW 100 to 630 kW
Regulation range
(Capacity range)
10 - 100%
Connection Solder Solder Solder or weld
Evaporating tem-
perature
– 60 to 60°C – 50 to 60°C – 40 to 60°C
Ambient temperature – 50 to 50 °C – 40 to 50 °C – 40 to 50 °C
Leak of valve seat < 0.02% of kv-value
MOPD 18 bar 22 bar 18 bar
Filter, replaceable
Internal
100 μm
External
100 μm
External
100 μm
Max. working
pressure
Ps = 42 bar
AKV 15-1,2,3:
Ps = 42 bar.
AKV 15-4:
Ps = 28 bar
Ps = 28 bar
Technical data
Expansion valves
Main data for the most standard products are briey described
below.
Further data can be found in the respective technical brochures.
Especially for valve dimensioning more information needs to be
obtained.
AKV10, AKV 15, AKV 20