Specifications

RK0YG302 © Danfoss 04/2007 185
AK-SM 350
Data
Type
Mea-
suring
points
Description Language Code No.
AK-SM 350 16
With inputs for
PT 1000 ohm &
PTC 1000 ohm
English, Ger-
man, French,
dutch, Italian
080Z8500
English (UK),
Spanish,
Portuguese,
English (US)
080Z8502
English,
Danish,
Swedish,
Finnish
080Z8503
m2+ 16 080Z8005
Printer cable 3 m (parallel) 080Z8401
Cable for PC
(see also AK-ST 500
literature)
RJ 45 - Com port 080Z0262
Ordering
Additional information!
Manual: RS8EF
Supply 115 V/230 V
+10/-15%, 50/60 Hz, 10 VA
Connection PT 1000 ohm at 0°C or
PTC 1000 ohm at 25°C or
NTC 5000 ohm at 25°C or
Termistor (-80 to 0, -40 to 40 or 0
to 100°C)
Digital On/O signal or
Standard 0 - 10 V /4 - 20 mA signal
Display Graphic LCD, 240 x 64
Direct measuring points 16
Total number of points 65
Measuring range, general -60 to +50°C
Measuring accuracy at Pt 1000 Resolution 0.1 K
Accuracy: +/- 0.5 K
Measuring interval 15, 30, 60, 120 or 240 minutes
Data capacity 55 log points, every 15 min. for 1
year
Battery backup Button cell for clock function
Power supply for e.g. pressure
transmitter
5 V max. 50 mA
12 V max. 50 mA
Pulse counter inputs for output
reading
Acc. to DIN 43864.
(Only for inputs 1 and 2)
Printer connection HP PCL-3, Parallel
Modem connection RJ 45
TCP/IP connection RJ 45
PC connection RJ 45
Data communication RS232, RS 485 (LON), RS 485 (MOD-
bus), RS 485 (TP) (TP= Third Party)
Relays Quantity 2
Max. load 24 V a.c. or 230 V a.c.
Imax (AC-1) = 5 A
Imax (AC-15) = 3 A
Enclosure IP 20
Ambient
environ-
ment
0 to 50°C, during operation
-20 to +70°C, during transport
20-80% RH, Non-condensed
No shock loads/vibrations
Approvals EN 60730-1 and EN 60730-2-9
EN 50081-1 and EN 50082-1
Weight 1.6 Kg
Important
Installation of data communication cables and repeaters must
comply with the requirements contained in the document:
Data communication between ADAP-KOOL® Refrigeration
system controls.
Number = RC8AC.