Specifications

20 RK0YG302 © Danfoss 05/2007
AK-PC 730
AK-PC 730
Additional information!
Manual: RS8EK
Ordering
Application
AK-PC 730 is particularly well-suited to capacity control of cascade
or booster systems.
By using two controllers, a complete capacity control of both
circuits is achieved.
Advantages
Start-up coordination ensures optimum interaction between
the high pressure and low pressure circuits in cascade/booster
systems
Start/stop signal for injection in cascade heat exchanger
Optimisation of suction pressure from the refrigeration area that
is used most
Optimisation of condenser in relation to ambient temperature
Error detection of dirty condenser
Flexible hardware platform with extension modules
Fast set-up using pre-dened set-ups
Control
Compressor capacity is controlled via the suction pressure P0, a
media temperature of S4 or an alternative control pressure Pctrl.
The reference can either be overide with a day/night signal or it
can be optimised automatically via the data communication.
Fan capacity is controlled either via the condensing pressure Pc
or a media temperature S7 (dry cooler). The reference can be
optimised via ambient temperature measurement and changed
during heat recovery.
The Ss and Sd sensors are used for monitoring of overheating of
suction pipe and pressure pipe temperature respectively.
Additional functions
Control of up to 4 compressor steps
Compressors of the same or dierent size
Speed control of one or two compressors
Equalising of operating time between compressors
Anti-cycle timers for each compressor
Up to 6 safety inputs per compressor
Capacity limit of compressors via two digital inputs
Step or speed control of up to 6 fans
Monitoring of fans
Coordination function between high-pressure and low-pressure
circuits
Injection signal for cascade heat exchanger
Monitoring of too low suction pressure P0 and of high condens-
ing pressure Pc
5 digital inputs for alarm monitoring
5 thermostats and pressure switches for monitoring/control
5 voltage inputs 0-10 V d.c. for signal monitoring
Type Function
Applica-
tion
Language Code no.
AK-PC 730 Capacity control
compres-
sor/con-
denser/
both
English,
German,
French, Italian,
Dutch
080Z0116
English (UK),
Spanish,
Portuguese,
English (US)
080Z0117
English (UK),
Danish,
Swedish,
Finnish
080Z0118