Specifications

36 RK0YG302 © Danfoss 05/2007 RGE
RGE
Type Code No. Refrigerants Motor rating
[A]
Voltage
[V]
No. of
phases
Current
[A]
Adj. range
[bar]
P-band
[bar]
Factory
setting [bar]
RGE-Z3T4-7DS 061H3050 R22/R404A/
R407C
0.2-7 A 200-240 3 7 A 116-406 psig/ 8-28 bar 4 bar 16 bar
RGE-X3R4-7DS 061H3006 R22/R404A/
R407C
0.2-5 A 380-415 3 5 A 116-406 psig/ 8-28 bar 4 bar 16 bar
RGE-Z1N4-5H 061H3013 R407C/R404A/
R134a/R22
0.2-2 A 200-240 1 2 A 116-406 psig/ 8-28 bar 4 bar 19 bar
RGE-Z1L4-7DS 061H3045
R407C/ R404A/
R134a/R22
0.2-2 A 200-240 1 2 A 116-406 psig/ 8-28 bar 6 bar 19 bar
RGE-Z1N4-7DS 061H3005 R407C/ R404A/
R134a/R22
0.2-4 A 200-240 1 4 A 116-406 psig/ 8-28 bar 4 bar 19 bar
RGE-Z3R4-7DS 061H3003 R407C/ R404A/
R134a/R22
0.2-5 A 200-240 3 5 A 116-406 psig/ 8-28 bar 4 bar 16 bar
RGE-Z1P4-7DS 061H3008 R407C/ R404A/
R134a/R22
0.2-6 A 200-240 1 6 A 116-406 psig/ 8-28 bar 4 bar 19 bar
RGE-Z1Q4-7DS 061H3009
R407C/ R404A/
R134a/R22
0.2-8 A 200-240 1 8 A 116-406 psig/ 8-28 bar 4 bar 19 bar
RGE-Z1L6-7DS 061H3048 R410A 0.2-2 A 200-240 1 2 A 16-39 bar/232-566 psig 9 bar 32 bar
RGE-Z1N6-7DS 061H3021 R410A
0.2-4 A 200-240 1 4 A 16-39 bar/232-566 psig 8 bar 32 bar
RGE-Z3R6-7DS 061H3027 R410A 0.2-5 A 200-240 3 5 A 16-39 bar/232-566 psig 8 bar 32 bar
RGE-Z1P6-7DS 061H3022 R410A
0.2-6 A 200-240 1 6 A 16-39 bar/232-566 psig 8 bar 32 bar
RGE-Z3T6-7DS 061H3051 R410A 0.2-7 A 200-240 3 7 A 16-39 bar/232-566 psig 8 bar 32 bar
RGE-Z1Q6-7DS 061H3023 R410A
0.2-8 A 200-240 1 8 A 16-39 bar/232-566 psig 8 bar 32 bar
RGE-X3R6-7DS 061H3028 R410A 0.2-5 A 380-415 3 5 A 16-39 bar/232-566 psig 8 bar 32 bar
RGE, Variable Speed Control, is used for fan speed control, and is
available in single and three phase versions. RGE is a simple and
ecient all-in-one pressure sensor and fan speed control, featur-
ing a reliable sensing mechanism using bellows. RGE is easy to
install and set up, and can be used for a large number of refrige-
rants: R 22, R 407C, R 404A, R 134a and R 410A. RGE is CE/EMC
approved.