Specifications
RK0YG302 © Danfoss 04/2007 41
Type Function Voltage Number Code No.
EKC 100
Temperature
controller
230 V 60 pcs 084B8610
115 V 60 pcs 084B8611
Ordering
Technical data
Electrical connection
Supply voltage 230 V a.c. +10/-15 %. 0.5 VA
Sensor connec-
tion
NTC 5000 ohm/25°C. e.g. type EKS 211
Accuracy
Measuring
range
-60 to +50°C
Controller
±1 K below -0°C
±0.5 K between -0 to +10°C
±1 K above +10°C
NTC sensor ±0.5 K at 0°C
Display LED, 2 digits
Light-emitting
diode (LED)
Indicates cut-in relay
Electrical con-
nection cable
Max.1,5 mm
2
multi-core cable on supply and relays.
Max. 1 mm
2
on sensors
Terminals are mounted on the circuit board
Relay
CE UL
Rated voltage 250 V 240 V a.c.
I 10 (6) A
10 A Resistive
5FLA 30LRA
The relay is a 16 A relay, but conductor lanes and
derating mean that 10 (6) A must not be exceeded
Environments
0 - 55°C, during operation
-40 - 70°C, during transport
20 - 80% Rh, not condensed
No shock inuence/vibrations
Enclosure
IP 20/IP 65 from front.
Buttons are imbedded in the front.
Approvals
EU Low Voltage Directive and EMC demands re CE-
marking complied with
LVD tested acc. EN 60730-1 and EN 60730-2-9, A1, A2
EMC tested acc. EN50082-1 and EN 60730-2-9, A2
NTC - temperature sensor type EKS 211:
(115 V a.c.)
Additional information!
Data sheet: RD8AZ
EKC 100