Specifications
48 RK0YG302 © Danfoss 05/2007
Additional information!
Manual: RS8DY
EKC 102
Weight = 170 g
Data
Supply voltage 230 V a.c.(115 V) +10/-15 %. 1.5 VA
Sensors
Pt 1000 or
PTC (1000 ohm/25°C) or
NTC-M2020 (5000 ohm/25°C)
Accuracy
Measuring range -60 to +99°C
Controller
±1 K below -35°C
±0.5 K between -35 to +25°C
±1 K above +25°C
Pt 1000 sensor
±0.3 K at 0°C
±0.005 K per grad
Display LED, 3 digits
Digital inputs
Signal from contact functions
Requirements to contacts: Gold plating
Cable length must be max. 15 m
Use auxiliary relays when the cable is longer
Electrical con-
nection cable
Max.1.5 mm
2
multi-core cable on supply and relays.
Max. 1 mm
2
on sensors - and DI inputs.
Terminals are mounted on the circuit board
Relays*
CE
(250 V a.c.)
UL **
(240 V a.c.)
DO1.
Refrigeration
10 (6) A
10 A Resistive
5FLA, 30LRA
DO2. Alarm/
Defrost/
Refrigeration
10 (6) A
10 A Resistive
5FLA, 30LRA
DO3. Fan 6 (3) A
6 A Resistive
3FLA, 18LRA
131 VA Pilot
duty
Environments
0 to +55°C, During operations
-40 to +70°C, During transport
20 - 80% Rh, not condensed
No shock inuence/vibrations
Enclosure
IP 65 from front.
Buttons and packing are imbedded in the front.
Approvals
EU Low Voltage Directive and EMC demands re CE-
marking complied with
LVD tested acc. EN 60730-1 og EN 60730-2-9, A1, A2
EMC tested acc. EN50082-1 og EN 60730-2-9, A2
* DO1 and DO2 are 16 A relays. DO3 is a 8 A relay. Max. load must be keept.
** UL-approval based on 30000 couplings
Type Function Supply Code No.
EKC 102A Temperature controller
230 V a.c. 084B8500
115 V a.c. 084B8503
EKC 102B Temperature controller with alarm function
230 V a.c. 084B8501
115 V a.c. 084B8504
EKC 102C
Temperature controller for electric defrost
230 V a.c. 084B8502
115 V a.c. 084B8505
EKC 102D
Controller for refrigeration with fan function
230 V a.c. 084B8506
115 V a.c. 084B8507
EKA 182A Copy key EKC - EKC 084B8567
Ordering