Specifications
RK0YG302 © Danfoss 04/2007 95
Data
Ordering
Additional information!
Manual: RS8CK
EKC 414A
The installation of data communications must comply with the require-
ments described in literature sheet no. RC8AC
*) a.c. 15 load acc. to EN 60947-5-1
Description Type Code no.
Refrigeration control controller with
plug connections and data communica-
tion
EKC 414A 084B8002
Display unit EKA 163B 084B8574
Display unit with operating buttons EKA 164B 084B8575
Cable for display unit (2 m with plug,
24 pcs)
084B7179
Cable for display unit (6 m with plug,
24 pcs)
084B7097
Realtime clock EKA 172 084B7069
Continued from previous page
Para
me-
ter
Service
The following readouts can be performed via the belonging parameter
Defrost sensor S5 S
def
u09 °C
Status on DI-input u10
Defrost time u11 min.
Air temperature S3 (S
in
) u12 °C
Status on night operation (on or o) u13
Status on ON-input u14
Status on DO-output u15
Air temperature S4 (S
out
) u16 °C
Thermostat temperature u17 °C
Thermostat cut-in time u18 min.
Temperature at S2 u20 °C
Superheat u21 K
Superheat reference u22 K
AKV valve’s actual opening degree u23 %
Evaporating pressure u25 bar
Evaporating temperature u26 °C
Supply voltage 230 V +10/-15%, 50/60 Hz, 5 VA
Sensors
Pt 1000 ohm for refrigerant temperatures
Pt 1000 ohm or PTC (R25 = 1000 ohm) for air tempera-
tures
Controller sen-
sor system
Measuring range -60 to +50°C
Accuracy
±0.5°C for sensor temperature =
-35 to +50°C
Display/ opera-
tion
The controller has no display or operating buttons on
front panel.
Operation takes place via a separate, connected display
or via data communication
It is possible to connect two displays with 0.1% reading
accuracy in the measuring range:
EKA 163, LED, three digits
EKA 164, LED, three digits, two operating buttons
1 digital input
If a contact function is connected, ir can be used for
door alarm, defrost start, night operation or start/stop of
the regulation
If other EKC 414 units are connected, coordinated de
-
frost can be performed via cable connections
1 digital output
May in conjunction with the digital input be used for
coordinated defrost via cable connections
230 V input
0 V: regulation stopped. The compressor relay, the de-
frost relay, the fan relay and the light relay are cut out.
230 V a.c.: regulation
(The function can be opted out).
Sensor connec-
tion
Sensors with AMP plug
AKV connection Max. 1 coil = 230 V. d.c.
Relays
Compressor relay
SPST NO, I
max.
= 6 A ohmic/ 3 A AC
15* inductive
Defrost relay
SPST NO, I
max.
= 6 A ohmic / 3 A
AC 15* inductive
Fan motor relay
SPST NO, I
max.
= 6 A ohmic / 3 A
AC 15* inductive
Light relay
SPST NO, I
max.
= 6 A ohmic / 3 A
AC 15* inductive
Alarm relay
SPDT, I
max.
= 6 A ohmic / 3 A AC
15* inductive
Environments
0 to +55°C, During operations
-40 to +70°C, During transport
20 - 80% Rh, not condensed
No shock inuence / vibrations
Mounting On DIN rail or on wall
Enclosure IP 20
Weight 0.4 kg
Approvals
EU Low Voltage Directive and EMC demands re CE-mark-
ing complied with.
LVD-tested acc. to EN 60730-1 and EN 60730-2-9
EMC-tested acc. to EN 50081-1 and EN 50082-2