Specifications
98 RK0YG302 © Danfoss 05/2007
Menu survey
SW: 1.0x
EKC 414A1
Function
Para
meter
Min. Max.
Factory
settings
Normal display
Shows the temperature at the selected sensor
Dene view in O17
-
°C
If you wish to see selected defrost stop
temperature, give the lower button a brief
push (1 sec.)
no= stop on temperature not selected
-
°C
Thermostat
Dierential r01 0.1 K 10.0 K 2.0
Max. limitation of thermostat’s setting tem-
perature
r02 -49°C 50°C 50.0
Min. limitation of thermostat’s setting tem-
perature
r03 -50°C 49°C -50.0
Temperature unit (°C/°F) r05 °C °F 0/°C
Correction of signal from S4 (S
out
) r09 -10.0 K 10.0 K 0.0
Correction of signal from S3 (S
in
) r10 -10.0 K 10.0 K 0.0
Start/Stop of refrigeration r12 OFF ON OFF
Reference displacement during night opera-
tion
r13
-20.0 K 20.0 K 0.0
Dene thermostat function
1=ON/OFF, 2=Modulating
r14
12 1
Denition and weighting, if applicable, of
thermostat sensors
100%=S4 (S
out
), 0%=S3 (S
in
).
The thermostat temperature can be seen in
U17
r15
0% 100% 100
Time between melt periods r16 0 h 10 h 1
Duration of melt periods r17 0 min 10 min. 5
Alarm
Alarm time delay A03 0 min. 120 min 30
Door alarm time delay A04 0 min. 90 min. 60
Time delay during cooling A12 0 min. 240 min 120
High alarm limit A13 -50°C 50°C 5.0
Low alarm limit A14 -50°C 50°C -30.0
Setting of the weighting between S3/S4 to
be used by the alarm function. The alarm
temperature can be seen in u57
A36 0% 100% 100
Compressor
Min. ON-time c01 0 min 50 min 0
Min. OFF-time c02 0 min 50 min 0
Defrost
Defrost stop temperature d02 0 25°C 6.0
Interval between defrost starts d03 OFF 48 h 8
Max. defrost duration d04 0 180 min 45
Time displacement of defrost cut-ins during
start-up
d05 0 240 min 0
Drip-o time d06 0 60 min 0
Fan start delay after defrost d07 0 60 min 0
Fan start temperature d08 -15 0°C -5.0
Fan cut-in during defrost (yes/no) d09 no yes no
Defrost sensor
0=S4 (S
out
) , 1=S5 (S
def
), 2=non. Stop on time
d10
02 2
Defrost at power up d13 no yes no
RTC module (if installed)
see RTC instructions
t01 to
t16
Injection control function
Max. value of superheat reference n09 3.0 K 15.0 K 12.0
Min. value of superheat reference n10 3.0 K 10.0 K 3.0
MOP temperature n11 -50.0°C 15°C/o 15°C
AKV valve’s time period
Should only be changed to OFF by trained
sta
n13
3 sec. 6 sec. 6
Adaptive control
Should only be changed to OFF by trained
sta
n14
OFF ON on
Average opening degree
Should only be changed by trained sta
n16 10%
75% 30.0
Start-up time for signal reliability
Should only be changed by trained sta.
n17
5% 70% 30.0
Stability factor for superheat control.
Changes should only be made by trained sta
n18
0104
Forced closing.. AKV valve shut in pos. ON n36 OFF ON OFF
Fan
Fan stop on compressor cut out F01 no yes no
Delayed fan stop when compressor is cut out F02 0 min 30 min 0
Safety function. The fan stops if the S5 tem-
perature reaches this value
F04 -50.0
50.0/
o
50.0
Miscellaneous
Delay of output signal after start-up o01 0 sec. 600 sec 5
Dene digital input signal (DI:
OFF=not used, 1=Door alarm, 2=defrost start,
3=Night operation, 4=External start/stop, 5 =
Coordinated defrost with cable connections,
6 = door function
o02 OFF 6 0
Network address (range = 0-60) o03 0 990 0
ON/OFF switch (service-pin message) o04 OFF ON OFF
Access code o05 OFF 100 OFF
Used sensor type for S3, S4 and S5 (Pt/PTC) o06 Pt Ptc 0/Pt
Set supply voltage frequency o12 50 Hz 60 Hz 50
Dene digitalt output signal (DO:
0=not used
Coordinated defrost with cable connections:
1=Master, 2= Slave
o13
02 0
Max. standby time after coordinated defrost o16 1 min 30 min 20
Display S4 % (S
out
)
0%=S3 (S
in
)
100%=S4 (S
out
)
The display temperature can be seen in u56
o17
0% 100%
100
Manual control of outputs:
OFF=No override
1: Compressor reay is ON (railheat relay = ON)
2: Defrost relay is ON
3: Fan relay is ON
4: Alarm relay is OFF (Railheat relay = on)
5: DO output is ON
6: AKV output is ON
7: Light relay is ON (Railheat = on)
When manual control is terminated, the set-
ting must be changed to OFF
o18
OFF 7 OFF
Pressure transmitter working range – min.
value
020 -1 bar 5 bar -1
Pressure transmitter working range – max.
value
021
6 bar 36 bar 12
Inject-ON denition
When the ON input is cut out refrigeration is
stopped.
Here you dene how the fan relay and the
alarm function are to act:
1 = Fan relay = ON, alarm monitoring active
2 = Fan relay = OFF, alarm monitoring active
3 = Fan relay = OFF, no alarm monitoring
4 = Fan relay = ON, no alarm monitoring
5 to 8= as 1 to 4, but without connection to
terminal 40-41.
o29 1 8 5
Refrigerant setting
1=R12. 2=R22. 3=R134a. 4=R502. 5=R717.
6=R13. 7=R13b1. 8=R23. 9=R500.
10=R503. 11=R114. 12=R142b. 13=User
dened. 14=R32. 15=R227. 16=R401A.
17=R507. 18=R402A. 19=R404A. 20=R407C.
21=R407A. 22=R407B. 23=R410A. 24=R170.
25=R290. 26=R600. 27=R600a. 28=R744.
29=R1270. 30=R417A
o30 0 30 0
Rail heat during day operation.
Setting of ON period in percentage of the
time in ”o43”
o41
0% 100% 100
Rail heat during night operation.
Setting of ON period in percentage of the
time in ”o43”
o42 0% 100% 100