Specifications

FIRE SAFETY DISTANCES
The stove must be installed in compliance with the following safety
conditions:
- minimum safety distance at the sides and back from medium-level
flammable materials: 40 cm
- easily flammable materials must not be located less than 80 cm from the
front of the stove
- if the stove is installed on a flammable floor, a sheet of heat insulating
material must be placed between the stove and the floor, which protrudes
by at least 20 cm at the sides and 40 cm at the front.
Objects made of flammable materials must not be placed on the stove or at
less than the safety distance from it.
If the smoke outlet pipe is connected to walls made of wood or other
flammable materials, it must be insulated with ceramic fibre or other
materials with similar characteristics.
AIR INTAKE
The room where the stove is located must have an air intake with cross
section of at least 80 cm
2 to ensure replenishment of the air consumed by
combustion.
SMOKE OUTLET
The stove must have its own smoke outlet (it must not discharge into common flues or other devices).
The smoke leaves the stove through the 8 cm diameter pipe at the back.
A T-section with condensation trap and bleeder must be fitted at the beginning of the vertical section.
The stove smoke outlet must be connected with the outside using black painted or steel pipes (resistant to
450°C), without obstructions.
The pipe seals must be air-tight. To seal and insulate (if necessary) the pipes, material that withstands up to
300°C must be used (silicone or high temperature mastic).
The horizontal sections may be up to 2 m long. Up to three 90° bends may be included.
If the smoke outlet does not end in a flue, a suitably fixed vertical section (at least 1.5 m long unless clearly
unadvisable for safety reasons) with wind guard at the end is essential. The vertical duct section may be indoor or
outdoor. If the smoke duct is outdoor, it must be insulated.
If the smoke duct ends in a flue, the flue must be authorized for solid fuel. If it is more than 150 mm in diameter,
it must be renewed by inserting an internal pipe and sealing the smoke outlet from the brickwork.
All sections of the smoke duct must be inspectable. If it is fixed, cleaning inspection openings must be provided.
The recommended installations are those shown in the following figures.
Smoke
1.5 m minimum h
Air intake from outside to room (minimum internal section: 80 cm
2
)
Brick-built flue
Air intake from outside to room (minimum internal section: 80 cm
2
)
9