Brochure

Edison Fuses Selection Guide and General Specifications
Description General Purpose – Midget General Purpose – Small Dimension Electronic
Fuse Type
Fast-Acting Time-Delay
Fast-Acting
Ceramic
Fast-Acting Glass
Medium Time-
Delay Glass
Time-Delay
Ceramic
Time-Delay
Glass
Fast-Acting
Glass
Time-
Delay
Glass
Part
Number
MCL MOL MEQ MEN ABC AGC GMA GMC MDA MDL S500 S506
Voltage
Rating
600 VAC 250 VAC 500 VAC 250 VAC
250 VAC
(0.5 to 30A)
125VDC:
(0.5 to 30A)
250VAC:
(0.1 to 10A)
32VAC:
(15 to 30A)
250VAC
(0.063 - 3A)
125VAC
(4 - 15A)
250VAC
(0.5 - 3A)
125VAC
(4 - 10A)
250VAC
125VDC
(20A)
250VAC:
(0.0625
to 8A)
32VAC:
(10 to 20A)
250VAC 250VAC
Amp Rating
0.5 to 50 0.5 to 30 0.25 to 30 0.5 to 30 0.5 to 30 0.10 to 30 0.063 to 15 0.5 to 10 0.5 to 20 0.0625 to 20 0.032 to 10 0.25 to 6.3
Interrupting
Rating
100,000
RMS Amps
10,000 RMS Amps See specifications table on product pages
Current
Limiting
N/A N/A
Agency
Approvals
UL Listed to 248.14, File E162443
CSA Cert. C22.2 Part 59.2, LR 700489
UL Listed standard 248-14
UL Listed Guide and File nos.
(ABC 0.25-20 A):
(AGC 1/100-10 A)
JDYX and E19180
UL Recognition Guide and
File nos. (ABC 20-30A):(AGC
11-30)
JDYX2 and E19180
CSA Certification Record No:
053787 C 000 and Class No:
1422 01 and 1422 30
Designed to UL/CSA 248-14
UL Listed, Guide JDYX, File
E19180 63mA-6A
UL Recognition, Guide JDYX2,
File E19180, 7A-15A
CSA Certified, File
053787_C_000,
63mA-6A Class 1422-01
UL Listed standard 248-14
UL Listed Card:
MDA 2/10-20A ,
MDL 1/16-8A
(Guide JDYX, File E19180
UL Recognized Card:
MDA 25-30A MDL 9-30A
(Guide JDYX2, File
E19180)
CSA Certification Card:
MDA 2/10-15A
(Class No. 1422-01)
UL Recognized Guide
JDYX2, File E19180
Semko Approval
VDE Approval
BSI Approval
IMQ Approval
RoHS compliant
RoHS
Dimensions
ferrule (in): 13/32 length (in): 1-1/2
1/4” x 1-1/4”,
(6.3mm x 32mm)
0.197” x 0.788”
(5mm x 20mm)
1/4” x 1-1/4”,
(6.3mm x 32mm)
0.197” x 0.788”
(5mm x 20mm)
Edison Fuses Selection Guide and General Specifications
Description
Current Limiting
Class J Class RK5 Class RK1 Class T Class L Class CC
Fuse Type
Fast-Acting Time-Delay Time-Delay Extremely Fast-Acting Fast-Acting Fast-Acting Time-Delay
Part Number JHL JDL ECNR ECSR LENRK LESRK TJN TJS LCU HCLR HCTR EDCC
Voltage
Rating
600VAC
450VDC
600VAC
300VDC*
250VAC
125 VDC*
(1-200A)
250VDC*
(201-600A)
600VAC
300VDC*
250VAC
125 VDC*
(10-60A)
250VDC*
(70-600A)
600VAC
300VDC*
300VAC
160 VDC
(15-600A)
600VAC 600V
600VAC
300VDC
(15-20A)
600VAC
600VAC
300VDC
(0.5-2.25A)
(20–30A)
Amp Rating
1 - 600 1 - 600 3 - 600 10 - 600 5 - 600 1 - 600 601 - 1200 0.5 - 30 0.25 - 30 0.5 - 30
Interrupting
Rating
200,000 RMS Symmetrical Amps
Current
Limiting
Class J Class RK5 Class RK1 Class T Class L Class CC
Agency
Approvals
UL Listed
Class J
Guide JDDZ
File E162363
CSA Certified
HRCI-J per
C22.2,
No. 248.8
File 700489
RoHS
compliant
UL Listed
Class J
Guide JDDZ
File E162363
CSA Certified
HRCI-J per
C22.2, No.
248.8
File 700489
UL Listed, Class RK, Guide JDDZ,
File E162363
CSA Certified HRCI-R per C22.2, No. 248.12,
File 700489
(LENRK CSA File 053787)
UL Listed, Class T,
Guide JDDZ, File E162363
CSA Certified HRCI-T per
C22.2, No. 248.12, File 53787,
Class 1422-02 & 1422-82
UL Listed,
Std. 248-10
CSA Certified,
HRC-L C22.2
No. 248.10,
Class 1422-02,
File 53787
UL Listed to 248.4, Class CC,
Guide JDDZ, File E162363,
CSA certified HRCI-MISC per C22.2
No. 248.4, File 700489
Dimensions
See product specification pages. ferrule (in): 13/32, length (in): 1-1/2
* Self-certified DC ratings
Line Overview
The Edison family of fuses, fuse blocks and fuse holders is di-
vided into two classes:
1. Current Limiting: Class CC, Class J, Class L, Class RK, Class T
2. General Purpose: Class M Midget and Small Dimension
The fuse selection guide below is a general summary of the
specifications included for each fuse type. This selection guide
does not include the many variables that can exist for specific
situations such as local codes, unusual temperature, or other
operating conditions. When selecting fuses, be sure to com-
ply with any applicable PUBLIC SAFETY standards that apply to
Overcurrent Protection Devices (OPD).
Selection Guide
1-800-633-0405
Circuit Protection
tCPR-142
For latest prices, please check AutomationDirect.com