QUAKER BRIDGE MALL LAWRENCEVILLE, NJ FOOD COURT AREA FIRE ALARM SYSTEM EQUIPMENT SUBMITTAL SUBMITTAL PREPARED BY SYSTEMS SALES CORPORATION 1345 CAMPUS PARKWAY MONMOUTH SHORES CORPORATE PARK NEPTUNE, NJ 07753-6815 (732) 751-0600 www.sscnj.com NEW JERSEY STATE FIRE ALARM PERMIT NO. P00525 ELECTRIC CONTRACTOR ARMOUR & SONS LANGHORNE, PA SSC Project No.
EST Catalog u EST3 Life Safety Platform EST3 Cabinets and Chassis 3-CAB series, 3-RCC series, 3-CHAS7 series, BC-1 3-RCC Series EN54-2:1997+A1 and EN54-4:1997+A1:2002+A2 pending 3-CAB Series Overview Standard Features EST3 has a wide selection of cabinet arrangements allowing the greatest use of EST3’s flexible modular design. Lobby enclosure wallboxes are manufactured from #14 AWG cold rolled steel with a gray baked enamel finish.
Application Lobby Enclosures EST3 lobby enclosures provide space for control, monitoring and display modules where they remain visible even with the door closed and secure. Ideal for mounting in lobby’s where appearance is important, maximum mounting flexibility is provided with doors that will mount for right or left hand opening. Lobby enclosures come in several sizes to match individual project requirements. The 3-CAB5 series semi-flush or surface mounts.
BC-1 Dimensions Ordering Information Catalog Number Equipment Mounting Space Description Battery Space Ship Wt. lb. (Kg) Two - 12V10A 30 (13.6) Four - 6V8A Two - 12V10A Two 12V17A 30 (13.6) 30 (13.6) 10 (4.5) 10 (4.5) 42 (19.1) 42 (19.1) 15 (6.8) 15 (6.8) 55 (25) 55 (25) 20 (9.1) 20 (9.
Accessories 3-BATS BC-1 3-BTSEN Detection & alarm since 1872 U.S. T 888-378-2329 F 866-503-3996 Canada Chubb-Edwards T 519 376 2430 F 519 376 7258 Southeast Asia T : +65 6391 9300 F : +65 6391 9306 BC-1EQ 3-CABEQ 3-RCCEQ50 3-RCCEQ65 3-TAMP Battery Shelf for RCC Enclosures. Takes one chassis space. Room for 3 (1.36) up to one 65 AH or two 50 AH batteries. Battery Cabinet - supports up to two 40 amp hour batteries. Battery sensor/distribution module 0.5 (.2) BC-1 - Seismic Battery hold down for BC-1.
GE Security EST Life Safety & Communications EST3 Multiplexed Fire Alarm System Overview Standard Features EST3 Power supplies consist of two assemblies, a high efficiency switch mode power supply card and a power supply monitor module. The monitor module mounts to the local rail and distributes the power from its supply to the local rail. The local rail distributes power from all power supplies to other local rail modules and user interface cards resulting in “Shared Power” throughout the system.
Application Engineering Specification The primary power supply provides the system with battery charging and voltage regulation. Software configures the charger to either 10-24 AH batteries or 30-65 AH batteries and controls the high/low charge rates. Batteries mounted in the same enclosure as the power supply, have their charge rate monitored and adjusted based on the local enclosure temperature, keeping charging rates within battery specification.
Typical Wiring Utility Power Primary Power Supply Power Supply Monitoring Booster Power Supply [1] 24Vdc * 2 x 3.5A 24Vdc * 2 x 3.5A Primary Power Supply Monitor Module [2] Booster Power Supply [2] 3 2 [2] 24Vdc * 2 x 3.5A 24Vdc * 2 x 3.5A Rails Power To Rail 4 Booster Power Supply Booster Power Supply Monitor Module Rails 1 4 3 2 4 1 Auxillary Power Takeoff 2 x 3.5A 3 2 1 4 3 2 1 Auxillary Power Takeoff 2 x 3.5A Auxillary Power Takeoff 2 x 3.
GE Security U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T +61 3 9239 1200 F +61 3 9239 1299 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.
GE Security EST Life Safety & Communications EST3 Multiplexed Fire Alarm System Overview Standard Features The 3-CPU3 is the Central Processing Unit Module monitoring the status of all modules and providing the link for network communications. Although each local rail card contains their own microprocessor, the 3-CPU3 provides all inter-module communication and has the ability to download rail module operating parameters.
Application Installation and Mounting The 3-CPU3 helps make EST3 an extremely powerful and flexible system. As a single node, stand alone system a single 3-CPU3 controls 1 to 19 local rail modules. For larger systems, up to 64 nodes interconnect on a peer-to-peer multi-priority token ring protocol network. J9 J8 Power Supply The 3-CPU3 controls all local panel responses to automatic, user initiated, or network reported events.
Typical Wiring To external supervisory input circuit To external alarm input circuit To external trouble input circuit NC C NO NO C N/A NC NO C NC SUP TROUBLE ALARM 1. Maximum #14 AWG (1.5 mm2) wire; minimum #18 AWG (0.75 mm2). 2. All shields, if used, must be continuous and insulated from ground, except at the originating panel. 3. Class A network data requires one pair of wires connecting the last node to the first node. 4.
GE Security U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T +61 3 9239 1200 F +61 3 9239 1299 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.com © 2009 General Electric Company All Rights Reserved Specifications 3-CPU3 Agency Listings UL, ULC, CSFM, CE, LPCB EN54* pending. Mounting 2 - Left most local rail spaces Terminal Size 18-12 AWG (1.0mm² to 2.
GE Security EST Life Safety & Communications EST3 Multiplexed Fire Alarm System Overview Standard Features The Modem Communicator is a two-way local rail module that performs a variety of off-premise communications functions for the EST3 system. • Listed for fire, security and access control • V.32bis 14.
Application Two versions of the Modcom are available: 3-MODCOM - Has an internal V.32bis 14.4K baud full duplex modem. The modem permits upload and download of system data remotely via a telephone line. In addition, the 3-MODCOM has a Digital Alarm Communications Transmitter (DACT) or dialer function that transmits network status information to Central Monitoring Stations (CMS) via telephone. Four DACT protocols are available: 1.
Specifications Agency Listings Installation Input Power Modem Protocol Dialer Protocol Pager Protocol (3-MODCOMP only) Telephone Dialing Connector CMS Telephone Numbers Quantity Available Digits Receivers Event Buffer Operating Environment Receivers Tested Format 4/2 and 3/1 Contact ID SIA DCS UL, FCC Part 68 / CFR 47, ULC. See Note 1. Takes up one LRM space in 3-CHAS7 24 Vdc @ 60mA standby, 95 mA active ITU - V.32bis 14.
GE Security U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T +61 3 9239 1200 F +61 3 9239 1299 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.com © 2009 General Electric Company All Rights Reserved 20 Data Sheet 85010-0107 Issue 5.1 Not to be used for installation purposes.
GE Security EST Life Safety & Communications EST3 Multiplexed Fire Alarm System Overview Standard Features The 3-SSDC1 and 3-SDDC1 Signature Driver Controller modules provide an intelligent interface between the 3-CPU3 module and Signature Series devices. Each module contains its own microprocessor used to coordinate, process and interpret information received from and sent to Signature devices. Power and communications is received directly from the control panel rail assembly.
Application The unique use of “BROADCAST POLLING” combined with “DIRECT ADDRESS SEARCH” ensures that only new information is transmitted allowing a reduced baud rate with fast response time. The low baud rate is ideal for retrofit applications since in most applications existing wiring can be used. During maintenance, should groups of detector heads be removed for service and returned into the wrong smoke detector base (location), the 3-SSDC1/3-SDDC1 will automatically detect the problem.
for maintenance and trouble conditions. Each smoke detector contains intelligence to adjust with environmental changes. This expands the amount of time required between cleaning while maintaining a constant alarm threshold. As the detector begins to exhaust the environmental compensation, and reaches the 80% level, the 3-SSDC1/3-SDDC1 will indicate a maintenance alert or dirty condition to the 3-CPU and indicate the specific device requiring cleaning.
GE Security U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T +61 3 9239 1200 F +61 3 9239 1299 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.com © 2009 General Electric Company All Rights Reserved Signature Series is a Trademark of GE Security. Engineering Specification The communication format between the control panel and analog devices shall be 100% digital.
GE Security EST Life Safety & Communications EST3 Multiplexed Fire Alarm System Overview Standard Features The EST3 audio amplifiers take full advantage of digital technology. Digital messages generated by the Audio Source Unit (ASU) and live paging messages are multiplexed into eight separate channels transmitted over a single twisted pair of wires.
Application EST3 zoned amplifier configurations offer improved system survivability and performance. Configuration provides improved survivability in the event of wiring faults that result in a loss of signaling. In the example shown in the diagram, a fault on the system using a central backed-up amplifier disables multiple signal/page circuits, and the standby amplifier is not able to bypass the fault. With EST3, the same fault removes the Audio Source Unit riser.
Specifications 3-ZA20A Agency Listing Environmental Frequency Response Output Voltage THD (distortion) Wire Size Internal Tone Generator SIGA-CC1/2 Support Standby Current Alarm Current Pwr. Ltd. Audio Output Wiring Configuration EOL Resistor Pwr. Ltd. 24 Vdc NAC Wiring Configuration 1120mA Class A or B (Style Z or Y) 15K Ohms in Class B Class A or B (Style Z or Y) Line Resistance, Max.* EOL Resistor Line Capacitance, Max Space Requirements 50 Ohms, Max. N/A 0.
GE Security U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T +61 3 9239 1200 F +61 3 9239 1299 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.com/est © 2009 General Electric Company All Rights Reserved 28 Data Sheet 85010-0057 Issue 8 Not to be used for installation purposes.
GE Security EST Fire & Life Safety EST3 Multiplexed Fire Alarm System Overview Standard Features The EST3 Control Display modules provide the emergency user with the simplest of interfaces, lights and switch control. The Control Display modules install over local rail modules. The local rail modules supply the power and drivers via a ribbon cable connection to the control display modules. The displays mount over any local rail module maximizing the flexibility of design layout.
Application Notes Control Display Modules come in a variety of types providing operational flexibility. There are five types of display modules available with EST3. Typically alarm zone annunciation appears on any of the first four module types shown. The first module supports simple zone annunciation; the second, zone annunciation with zone disable; the third, alarm and trouble zone annunciation, the fourth alarm and trouble zone annunciation with zone disable.
Engineering Specification The Life Safety system shall incorporate annunciation of Alarm, Supervisory, Trouble and Monitor operations. Annunciation must be through the use of LED display strips complete with a means to custom label each LED as to its function. Where applicable control of remote smoke control devices must be made available at the control center. Switches with LEDs must provide positive feed back to the operator of remote equipment status.
GE Security U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T 61 3 9259 4700 F 61 3 9259 4799 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.
EST Catalog u EST3 Life Safety Platform Audio and Telephone Masters 3-ASU series Overview Standard Features The efficient EST3 audio system provides for intuitive local and remote audio control for Mass Notification/Emergency Communications (MNEC), Life Safety and other approved uses. EST3 audio builds from standard modules that fit together easily. Audio components use standard EST3 cabinets and power supplies.
Application EST3 audio is accomplished by selecting modular components for installation in standard fire alarm cabinet assemblies. At the main control panel location mounting audio control equipment provides an emergency user interface for “Paging” and optionally a “Firefighters Master Telephone”. Zoned amplifiers mount in the main control panel and/or in remote nodes. By mounting amplifiers in remote nodes, wire runs and space requirements are reduced at the main control panel.
Installation and Mounting Typical Wiring Typical Fire Fighter's Telephone Circuit ULI/ULC Listed 47K ohm EOL Resistor J3 J4 BIN J2 CIN AIN AOUT J5 J6 DIN J7 BOUT J9 J8 10 9 Twisted Shielded Pair if run with other wiring J11 J10 J1 READY TO PAGE CC1 8 7 6 5 4 3 2 1 ALL CALL Page to Evac To Signature Data Circuit To Phones Page to Alert All Call Minus COUT DOUT Page by Phone J8 J9 J9 J8 J11 10 9 J10 CC1 NC C NO NO C N/A NC NO C NC SUP TROUBLE ALARM 8 7 6 5 4 3 2 1 Connect to T
Specifications Detection & alarm since 1872 U.S. T 888-378-2329 F 866-503-3996 Canada Chubb-Edwards T 519 376 2430 F 519 376 7258 Catalog Number Agency Listings Ambient Temp.
EST Catalog u EST3 Life Safety Platform EST3 Remote Annunciators 3-ANNCPU3, 3-LCDANN, 3-6ANN, 3-10ANN, 3-EVxxx, 3-4ANN EN54-2:1997+A1 and EN54-4:1997+A1:2002+A2 pending Overview Application EST3 supports a full range of annunciator options for Mass Notification/Emergency Communication (MNEC), Life Safety and other purposes. Annunciator cabinets are constructed from 16 gauge cold rolled steel. The gray textured enamel finish of the annunciators complements any decor.
Typical Wiring Graphic Annunciator Field Wiring Rear view 3-ANNCPU3 Field Wiring 3-6ANN Shown 2 3 4 5 6 NETWORK A 7 8 To Backbox 9 1 RS-485 NETWORK DATA TO NEXT PANEL 24VDC TO NEXT POWER MODULE 24VDC FROM 3-PPS/M OR 3-BPS/M POWER RISER 1 NETWORK B SPARE 24 VDC 1 24 VDC EARTH GROUND Ground Lead RS-485 NETWORK DATA FROM PREVIOUS PANEL 1 Power limited circuit Graphic Annunciator 10 To TB1 on 3-ANNCPU3 TX RX TX RX TX RX TX RX RX TX RX TX RX TX RX TX NOTES: 1.
Dimensions 6.12 in (15.55 cm) Semiflush Mount Surface Mount 2.75 in (6.99 cm) 2.75 in (6.99 cm) 0.46 in (1.17 cm) 7.60 in (19.31 cm) 7.60 in (19.31 cm) TOP RCLM/B(-S) TOP Earth ground stud located on inside upper left corner next to knockout 12.07 in (30.66 cm) 12.95 in (32.9 cm) Earth ground stud located on inside upper left corner next to knockout 12.95 in (32.9 cm) Semiflush Surface mount 10.1 in. (25.7 cm) 11.6 in. (29.4 cm) 2.75 in. (7.0 cm) 2.75 in. (7.0 cm) 11.6 in. (29.
Ordering Information Catalog Ship Wt. Description Number lb (kg) Command Module Annunciators (Come with CPU, LCD display and doors. Order wallbox separately.) 3-LCDANN 3-LCDANN-E Remote LCD Command Module Annunciator. Remote LCD Command Module Annunciator. For EN54* market only, CE. 3.8 (1.7) 3.8 (1.7) Base Annunciators (Come with two 3-ANNSM annunciator support modules, a CPU, and doors. Order Display/Control modules, additional support modules & wallbox separately.) Detection & alarm since 1872 U.S.
BCA Battery Cabinet Accessory The BCA Battery Cabinet Accessory is designed for the professional installation of systems requiring battery storage and meets the requirement of NFPA 72 (1-5.2.9) standby battery storage for battery backup. The BCA allows for easy access and maintenance of the batteries while also assisting against unnecessary power drain, interference or degeneration of the battery. The unit can be mounted securely to a wall, preventing mechanical injury or damage to other equipment.
Specifications: The BCA Battery Cabinet Accessory is constructed of 16 gauge (.062 thk.) cold rolled steel and finished with a complete interior and exterior durable red or black textured, heat-resistant baked-on enamel finish. The front cover features a full length stainless steel piano hinge and includes a high security CAT 45 keyed door lock. Overall dimensions measure 22” wide by 10” high by 8 1/2” deep. Four 1/2” and 3/4” EMT conduit knockouts are located on the sides and back.
Rechargeable Sealed Lead-Acid Battery PRB1255 12 Volt 55 Amp. Hrs. Features: Absorbent Glass Mat (AGM) technology for superior performance. Valve regulated, spill-proof construction. Power/volume ratio yielding unrivaled energy density. Built-in (recessed) battery handles for safe and easy transport Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certified. U.L. recognized under file number MH 14328. PERFORMANCE SPECIFICATIONS Nominal Voltage.............................................
TECHNICAL DATA: PRB1255 CONSTANT POWER DISCHARGE RATINGS WATTS PER CELL @ 25” C FINAL VOLTAGE MODEL PS-12550 5 10 MIN MIN 15 20 MIN MIN 210 184 153 115 87 72 225 190 158 118 89 73 1.67 354 230 194 160 120 90 74 Shelf Life and Storage Capacity Retention Ratio (%) o o Terminal Voltage 13.0 12.0 11.0 10.0 27.5A Final Voltage 11A 5.5A 2.75A 55A 110A 6 12 MIN 342 Ambient Temperature 20 C (68 F) 2.4 60 MIN 320 14.0 1.2 45 1.70 Discharge Characteristics 8.
EST Catalog u Power Supplies and Accessories Remote Booster Power Supplies BPS6A, BPS10A Overview Standard Features The Booster Power Supply (BPS) is a UL 864, 9th Edition listed power supply. It is a 24 Vdc filtered-regulated, and supervised unit that can easily be configured to provide additional notification appliance circuits (NACs) or auxiliary power for Mass Notification/ Emergency Communication (MNEC), as well as life safety, security, and access control applications.
Application Dimensions The BPS provides additional power and circuits for notification appliances and other 24 Vdc loads. It is listed for indoor dry locations and can easily be installed where needed. D5 Fault conditions are indicated on the on-board diagnostic LEDs, opening the BPS input sense circuit and the trouble relay (if programmed). While this provides indication to the host system, the BPS can still be activated upon command.
Typical Wiring Single or cascaded booster anywhere on a notification appliance circuit To next signaling device, booster, or EOL resistor NAC Circuit NAC Circuit Fire Alarm Control Panel Sense 2 Input Sense 1 Input Existing NAC end-of-line resistors are not required to be installed at the booster’s terminals. This allows multiple boosters to be driven from a single NAC circuit without the need for special configurations.
Specifications Model AC Line Voltage Detection & alarm since 1872 Notification Appliance Circuit Ratings U.S.
EST Catalog u Intelligent Input-Output Synchronization Output Module SIGA-CC1S, MCC1S MEA Patented Overview Standard Features SIGA-CC1S and MCC1S Synchronization Output Modules are intelligent analog addressable devices that form part of EST’s Signature line of products. The actual operation of the SIGA-CC1S and MCC1S is determined by the “personality code” selected by the installer, which is downloaded to the module from the Signature loop controller during system configuration.
Application Installation The SIGA-CC1S mounts to a standard North American two-gang electrical box, making it ideal for locations where only one module is required. Separate I/O and data loop connections are made to each module. The SIGA-CC1S: mounts to North American 2-1/2 inch (64 mm) deep 2-gang boxes and 1-1/2 inch (38 mm) deep 4 inch square boxes with 2-gang covers and SIGA-MP mounting plates. The terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size.
Typical Wiring SIGA-CC1S (Standard Mount) Personality Code 5 SIGA-MCC1S (UIO Mount) Typical Speaker Circuit Personality Code 5 Typical Speaker Circuit UL/ULC Listed 47KW EOL UL/ULC Listed 47KW EOL Personality Code 6 Personality Code 6 Typical Telephone Circuit Typical Telephone Circuit UL/ULC Listed 47KW EOL UL/ULC Listed 47KW EOL Personality Code 25 Enhanced Integrity and Genesis Devices Enhanced Integrity and Genesis Devices Personality Code 25 UL/ULC Listed 47KW EOL UL/ULC Listed 47KW EOL
Specifications Catalog Number Detection & alarm since 1872 U.S. T 888-378-2329 F 866-503-3996 Canada Chubb-Edwards T 519 376 2430 F 519 376 7258 Southeast Asia T : +65 6391 9300 F : +65 6391 9306 India T : +91 80 4344 2000 F : +91 80 4344 2050 Australia T +61 3 9239 1200 F +61 3 9239 1299 Europe T +32 2 725 11 20 F +32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 utcfireandsecurity.com © 2010 UTC Fire & Security. All rights reserved.
Rechargeable Sealed Lead-Acid Battery PRB127 12 Volt 7.0 Amp. Hrs. Features: Absorbent Glass Mat (AGM) technology for superior performance. Valve regulated, spill proof construction allows safe operation in any position. Power/volume ratio yielding unrivaled energy density. Rugged plastic case and cover Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certified. U.L. recognized under file number MH 20845. PERFORMANCE SPECIFICATIONS Nominal Voltage.........................................
TECHNICAL DATA: PRB127 Discharge Characteristics (V) 100 Charging is not necessary unless 100% of capacity is required. o Charging before 5C use is necessary o (41 F) to help recover full capacity. 80 60 40oC (104oF) 40 o 30 C o (86 F) 14.0 12.0 11.0 10.0 1.4A 3.5A 9.0 Final Voltage 8.0 0 0 2 o 13.0 Charge may fail to restore full capacity. Do not let batteries reach this state.
EST Catalog Intelligent Initiating Devices Intelligent Smoke Detector with Optional CO Sensor SIGA2-PS, SIGA2-PCOS Overview Standard Features Signature Series SIGA2-P(CO)S photoelectric detectors bring advanced sensing technology to a practical design that increases efficiency, saves installation time, cuts costs, and extends life safety and property protection capabilities.
Application Sensing and reporting technology Smoke detection The SIGA2-PS detects extremely small particles of combustion and triggers an alarm at the first sign of smoke. Thanks to its highperformance forward scattering reflective response technology, the photoelectric smoke sensor responds quickly and reliably to a wide range of fire types, especially slow burning fires fuelled by combustibles typically found in modern multi-use buildings.
Typical Wiring The detector mounting bases accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG (1.5mm2), and #12 AWG (2.5mm²) wire sizes. Note: Sizes #16 AWG (1.0mm ) and #18 AWG (0.75mm ) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications.
Compatibility SIGA2-P(CO)S detectors are compatible only with the Signature Loop Controller. Detection & alarm since 1872 Warnings & Cautions U.S. T 888 378 2329 F 866 503 3996 This detector will not operate without electrical power. As fires frequently cause power interruption, we suggest you discuss further safeguards with your fire protection specialist.
EST Catalog Intelligent Initiating Devices Intelligent Heat Detectors with Optional CO Sensors SIGA2-HFS, SIGA2-HRS, SIGA2-HCOS Overview Standard Features Signature Series fixed temperature and rate-of-rise heat detectors bring advanced sensing technology to a practical design that increases efficiency, saves installation time, cuts costs, and extends property protection capabilities.
Application Sensing and reporting technology Heat detection SIGA2-HRS rate-of-rise heat detectors provide a 15 °F (9 °C) per minute rate-of-rise heat sensor for the detection of heat due to fire. The heat sensor monitors the temperature of the air and determines whether an alarm should be initiated. The microprocessor in each detector provides four additional benefits - Self-diagnostics and History Log, Automatic Device Mapping, Stand-alone Operation and Fast, Stable Communication.
Typical Wiring The detector mounting bases accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG (1.5mm2), and #12 AWG (2.5mm²) wire sizes. Note: Sizes #16 AWG (1.0mm ) and #18 AWG (0.75mm ) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications.
Warnings & Cautions • This detector does not operate without electrical power. As fires frequently cause power interruption, discuss further safeguards with the local fire protection specialist. • This detector does not sense fires in areas where heat cannot reach the detector. Heat from fires in walls, roofs, or on the opposite side of closed doors may not reach the detector.
EST Catalog u Intelligent Initiating Intelligent Duct Smoke Detector SIGA-SD MEA Overview Standard Features The Edwards SuperDuct Signature Series smoke detector is the most advanced and most reliable device in its class. Designed for easy installation and superb reliability, SuperDuct represents the perfect balance of practical design and advanced technology.
Application SuperDuct detectors are ideally suited to duct smoke detection applications where early indication of combustion is required within the confined space of ventilation ductwork. Its primary purpose is to provide early warning of an impending fire and to prevent smoke from circulating throughout the building. It is typically used to detect smoke in the supply side of the HVAC system but can provide supervision of the return side as well.
Assembly Mounting Sampling tube socket Detector HVAC duct Airflow Exhaust tube socket Detector Exhaust tube Thin gasket Sampling tube Thick gasket Coupling Sampling tube (ordered separately) #10 sheet metal screw (2X) Plug Wiring SIGA-LED [1] Alarm or 1 Alarm Auxiliary equipment 2 Test SD-TRK or SD-TRM [1] 3 4 17 16 15 Data Out ( ) Data Out ( ) Data In ( ) Data In ( ) 14 13 12 11 10 9 8 7 Notes [1] No more than one remote test station or LED indicator can be connected to the de
Specifications, detector Dimensions Detection & alarm since 1872 U.S. T 888-378-2329 F 866-503-3996 Canada Chubb-Edwards T 519 376 2430 F 519 376 7258 Southeast Asia T : +65 6391 9300 F : +65 6391 9306 India T : +91 80 4344 2000 F : +91 80 4344 2050 Australia T +61 3 9239 1200 F +61 3 9239 1299 Europe T +32 2 725 11 20 F +32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 utcfireandsecurity.com © 2010 UTC Fire & Security. All rights reserved.
EST Catalog u Intelligent Input/Output Control Relay Modules SIGA-CR, SIGA-MCR, SIGACRR, SIGA-MCRR MEA SIGA-CR SIGA-MCR Overview Standard Features The Control Relay Module and the Polarity Reversal Relay Module are part of the Signature Series system. They are intelligent analog addressable devices available in either plug-in (UIO) versions, or standard 1-gang mount versions.
Installation Application SIGA-CR and SIGA-CRR: modules mount to North American 2½ inch (64 mm) deep 1-gang boxes and 1½ inch (38 mm) deep 4 inch square boxes with 1-gang covers and SIGA-MP mounting plates. The terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size. The operation of Signature Series control relays is determined by their sub-type code or “Personality Code.” Personality Code 8: CONTROL RELAY (SIGA-CR/MCR) - Dry Contact Output.
Typical Wiring Modules will accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG (1.50mm2) and #12 AWG (2.5mm2) wire sizes. Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. Notes 1 Refer to Signature Loop Controller Installation Sheet for wiring specifications. 2 NFPA 72 requires that the SIGA-CR/SIGA-MCR be installed in the same room as the device it is controlling.
Typical Wiring Modules will accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG (1.50mm2) and #12 AWG (2.50mm2) wire sizes. Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications.
Specifications Catalog Number SIGA-CR SIGA-MCR Description Control Relay Type Code Personality Code 8 (Factory Set) SIGA-MCRR Polarity Reversal Relay Address Requirements Personality Code 8 (Factory Set) Uses 1 Module Address Operating Current Standby = 100µA Activated = 100µA Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal) Relay Type and Rating Mounting SIGA-CRR Form “C” 24 VDC = 2 amps (pilot duty) 120 Vac = 0.5 amps 220 Vac (non-UL) = 0.
Signature Series Overview Detection & alarm since 1872 U.S. T 888-378-2329 F 866-503-3996 Canada Chubb-Edwards T 519 376 2430 F 519 376 7258 Southeast Asia T : +65 6391 9300 F : +65 6391 9306 India T : +91 80 4344 2000 F : +91 80 4344 2050 Australia T +61 3 9239 1200 F +61 3 9239 1299 Europe T +32 2 725 11 20 F +32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 utcfireandsecurity.com © 2010 UTC Fire & Security. All rights reserved.
EST Catalog u Intelligent Input-Output Input Modules SIGA-CT1, SIGA-CT2 & SIGAMCT2 SIGA-CT1/2 SIGA-MCT2 MEA S CHINA Application Notes Available Overview Standard Features The SIGA-CT1 Single Input Module and SIGA-CT2/SIGA-MCT2 Dual Input Modules are intelligent analog addressable devices used to connect one or two Class B normally-open Alarm, Supervisory, or Monitor type dry contact Initiating Device Circuits (IDC).
Signature Series Overview UIO Motherboard The Signature Series intelligent analog-addressable system from Edwards Security is an entire family of multi-sensor detectors and mounting bases, multiple-function input and output modules, network and non-network control panels, and user-friendly maintenance and service tools. Analog information from equipment connected to Signature devices is gathered and converted into digital signals.
Typical Wiring Modules will accept #18 AWG (0.75mm2), #16 (1.0mm2), and #14AWG (1.50mm2), and #12 AWG (2.50mm2) wire sizes. Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. Initiating (Slave) Device Circuit Wire Specifications Maximum Allowable Wire Resistance Maximum Allowable Wire Capacitance For Design Reference: 50 ohms (25 ohms per wire) per Circuit 0.
Specifications Detection & alarm since 1872 U.S.
RIC Coil Energized LED RIC-1, RIC-2 Series Relay Multi-Voltage Relay Module The RIC-1 and RIC-2 are ideal for applications where remote relays are required for control or status feedback. They are suitable for use with HVAC, temperature control, fire alarms, security, energy management and lighting control systems. The SSU-RIC-1 Relay, SPDT, provides 10.0 Amp resistive form C contacts. The relay coil may be energized by one of three input voltages: 24VDC, 24VAC, or 115VAC.
EST Catalog u Strobes, Horns, Bells, Chimes Field Configurable Horns and Strobes Genesis Series Pending MNEC appliances available with clear or amber lenses. Overview Standard Features The Genesis line of fire alarm and mass notification/emergency communications (MNEC) signals are among the smallest, most compact audible-visible life safety signaling devices in the world. About the size of a deck of playing cards, these devices are designed to blend with any decor.
Application Installation Genesis strobes are UL 1971-listed for use indoors as wall-mounted public-mode notification appliances for the hearing impaired. Prevailing codes require strobes to be used where ambient noise conditions exceed 105 dBA (87dBA in Canada), where occupants use hearing protection, and in areas of public accommodation as defined in the Americans with Disabilities Act (see application notes – USA).
Current Draw Strobes, Horn-Strobes Horns Multi-cd Wall Strobes (G1-VM) 15 cd* 30 cd* 15/75 cd** UL Rating RMS RMS RMS 16 Vdc 103 141 152 16 Vfwr 125 179 224 *G1-VM multi-cd; **G1F-V1575 fixed 15/75 cd Typical Current 16 Vdc 20 Vdc 24 Vdc 33 Vdc 16 Vfwr 20 Vfwr 24 Vfwr 33 Vfwr 15 cd RMS 85 71 59 46 119 103 94 87 30 cd RMS 127 98 82 64 169 143 129 112 15/75 RMS 150 123 104 84 223 189 169 148 75 cd* RMS 255 346 110 cd* RMS 311 392 75 cd RMS 245 188 152 112 332 253 218 179 110 cd RMS 285 240 191 137 37
Average Sound Output (dBA) dBA output (High dB setting, anechoic, 24V, measured at 10ft) Temporal Horns, Horn-strobes (G1-HD, G1-HDVM series) High dB Setting 16 Vdc 24 Vdc 33 Vdc UL464 Temporal Steady 81.4 84.4 86.3 85.5 88.6 90.4 UL464 Low dB Setting Temporal Steady 16 Vdc 24 Vdc 33 Vdc 76.0 79.4 82.1 80.1 83.5 86.5 Average Temporal/ Steady 91.4 94.5 96.9 Peak Temporal/ Steady 94.2 97.6 99.5 Average Temporal/ Steady 86.3 89.8 92.5 Peak Temporal/ Steady 89.2 92.5 95.
Fire appliances available with white or red housings. MNEC appliances available with clear or amber lenses. Ordering Information Model Housing Marking Lens Strobe Horn Ship Wt.
Detection & alarm since 1872 U.S. T 888-378-2329 F 866-503-3996 Canada Chubb-Edwards T 519 376 2430 F 519 376 7258 Southeast Asia T : +65 6391 9300 F : +65 6391 9306 India T : +91 80 4344 2000 F : +91 80 4344 2050 Australia T +61 3 9239 1200 F +61 3 9239 1299 Europe T +32 2 725 11 20 F +32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 utcfireandsecurity.com © 2010 UTC Fire & Security. All rights reserved. 83 85001-0573 D ATA S H E E T Not to be used for installation purposes.
EST Catalog u Speakers, Telephones Genesis Speakers and Strobes Genesis G4 Series MEA PENDING Patents pending Overview Standard Features The Genesis line of life safety and mass notification/emergency communications (MNEC) signals are the smallest, most compact audible-visible emergency signaling devices in the world. Protruding no more than one inch from the wall, Genesis speakers and speaker-strobes blend with any decor.
Speaker Application Strobe Application The suggested sound pressure level for each signaling zone used with alert or alarm signals is a minimum of 15 dB above the average ambient sound level or 5 dB above the maximum sound level having a duration Typical Sound Output of at least 60 seconds, Distribution dBA whichever is greater. This Measured in anechoic chamber at two watts is measured 5 feet (1.5 m) above the floor.
Light output Wiring Per cent of UL rating versus angle Field wiring is connected to Genesis signals with terminals that accommodate #18 toSpeaker-only #12 AWG (0.75 mm² to 2.5 mm²) wiring. Wiriing % Of Candela H Spec. % Of Candela V Spec. To listed fire alarm control panel Speaker-only Wiriing (supervised amplifier signal circuit – 25.2 or 70.7V rms) To listed fire alarm control panel (supervised amplifier signal circuit – 25.2 or 70.
Ordering Information Model U.S. T 888-378-2329 F 866-503-3996 Canada Chubb-Edwards T 519 376 2430 F 519 376 7258 Southeast Asia T : +65 6391 9300 F : +65 6391 9306 India T : +91 80 4344 2000 F : +91 80 4344 2050 Australia T +61 3 9239 1200 F +61 3 9239 1299 Europe T +32 2 725 11 20 F +32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 utcfireandsecurity.com © 2010 UTC Fire & Security. All rights reserved.