E-PDD Duct Smoke Detector Installation Sheet 
Operation 
The duct smoke detector's primary purpose is to provide early 
warning of an impending fire and shut down the HVAC unit in 
order to prevent smoke from circulating throughout the 
building. The duct smoke detector is designed for use in duct 
applications where temperatures can exceed standard detector 
capabilities. 
Air is introduced to the duct smoke detector's sensing chamber 
through a sampling tube that extends into the HVAC duct and 
is directed back into the ventilation system through an exhaust 
tube. The difference in air pressure between the two tubes 
pulls the sampled air through the sensing chamber. When a 
sufficient amount of smoke is detected in the sensing chamber, 
the duct smoke detector notifies the fire alarm control panel.  
The device address is set using the two rotary switches located 
on the front of the unit. One device address is required. 
The detector is capable of performing comprehensive self-
diagnostics and storing the results. 
In installations where the duct smoke detector’s controls and 
indicators are hidden from view, a remote test station or an 
LED indicator can be connected to the detector to provide 
these functions. 
Jumper setting operation 
The following jumper settings determine the operation of the 
detector. 
Figure 1: Jumper setting 
JP3
3  2 1
Table 1:Jumper settings 
Settin
g   Operation   Description 
1
-2  Alarm  
Factory Default: Configures the detector 
for alarm latching operation 
2
-3  Supervisory 
Configures the detector for supervisory 
operation 
LED operation 
The detector provides two LEDs, visible from the front side of 
the detector, that show its status. 
LED
  Description 
Power LED
  Off when the detector is in the alarm state 
Flashes intermittently when the detector is in 
the normal state 
Alarm/active LED
Indicates the detector is in the alarm/active 
state as follows: 
Flashes at a continuous rate if the first 
detector is in alarm/active 
Flashes intermittently if not the first detector 
in alarm/active 
Installation 
WARNINGS 
•  The duct smoke detector is not intended as a substitute for 
open area protection. 
•  This detector will not operate without electrical power. As 
fires frequently cause power interruption, you should 
discuss further safeguards with your local fire protection 
specialist. 
•  The duct smoke detector will not operate as designed 
outside of the listed electrical and environmental 
specifications. 
•  The duct smoke detector will not sense smoke unless the 
ventilation system is operating and the sensor’s cover is 
properly installed. 
•  The duct smoke detector may not operate as designed 
unless installed in accordance with these instructions and 
all applicable national and local codes as determined by 
the local authority having jurisdiction. 
Note: Read these instructions thoroughly before installing. In 
addition to this document, important information can be found 
in Technical Bulletin P/N 3101212. 