User Manual
P/N 3101210 • REV 02 • ISS 28JAN13    3 / 6 
5.  Mount the duct smoke detector on the HVAC duct and 
secure it using two sheet metal screws provided. 
6.  If using an air sampling tube that is longer than the width 
of the duct, cut the tube so that approximately one inch of 
the tube extends through the duct. Seal the opening 
around the tube with an approved duct sealant as shown 
in Figure 4. 
Figure 4: Duct detector installation 
HVAC duct
Airflow
Sampling
tube
Detector
#10 sheet metal screw (2X)
Figure 5: Sampling tube support 
HVAC
duct
Sampling
tube
Exhaust tube
Plug
Detector
Sealant
Airflow
   36 in≥
7.  Verify that all field wiring is free of opens, shorts, and 
ground faults. 
8.  Make all wiring connections as shown in “Wiring.” 
9.  Set the module address as follows: 
Use a screwdriver to adjust the two rotary switches on the 
front of the module. Set the TENS rotary switch (0 through 
12) for the 10s and 100s digit and the ONES rotary switch 
for the 0 through 9 digit. For example: device address 21, 
set TENS rotary switch to 2 and set the ONES rotary 
switch to 1. 
Refer to “Specifications” for available address numbers. 
Figure 6: Duct detector address 
0
1
2
3
4
5
6
12
11
10
9
8
7
0
9
1
2
3
4
5
6
7
8
Insert screwdriver here
10.  Set jumper JP3 to appropriate position. Refer to 
“Operation.” 
11.  Verify the air pressure differential value falls within the 
specified operating range of the detector in accordance 
with procedures specified in “Maintenance and testing.” 
12.  After completing installation of the duct smoke detector, 
test the detector to ensure it is operating correctly in 
accordance with procedures specified in “Maintenance 
and testing.” 
Maintenance and testing 
Verify the air pressure differential: 
In order to verify air pressure differential, air must be moving 
through the HVAC system. 
To verify the air pressure differential: 
1.  Connect a suitable air pressure differential meter to the 
sampling tube and exhaust tube openings as shown in 
Figure 7. 
2.  Verify that the air pressure differential measured falls 
within the specified operating range of the detector.  
3.  If the air pressure differential measured does not fall within 
the specified operating range of the detector, make sure 
the sampling tube air holes are not obstructed and are 
facing the HVAC system airflow. 






