Instruction Manual

2 / 4 P/N 3100613 • REV 05 • REB 30JAN13
Figure 2: Strobe settings
1. JP1: Strobe signal output: Cut to change from 1 flash per second
(public mode) to temporal (private mode)
Note: If the strobe is set to temporal (private mode), this
device is no longer UL 1971 or CAN/ULC-S526 Listed or FM
Approved but is UL 1638 Listed.
Figure 3: UL 1971 minimum light output (% of rating vs. angle)
1. Angle
2. Percentage of rated output
Note: Horizontal and vertical outputs have the same pattern
Wiring
Caution: For proper supervision of fire alarm circuitry, break
wires at S+ and S−. See Figure 4.
Figure 4: Wiring diagram
1. From previous device or control panel
2
. To next device, EOL or circuit return
Note: Signal polarity is shown in the alarm condition.
Figure 5: Mounting diagram
Table 3: Strobe operating current in RMS (A)
95 cd 115 cd 150 cd 177 cd
VDC
0.330 0.392 0.502 0.565
VFWR
0.432 0.518 0.643 0.693
VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified
Operating currents shown above were measured by UL at 16 VDC and
16 VFWR.
100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
5
10
15
20
25
3
0
3
5
4
0
4
5
50
55
60
65
70
75
80
85
90
9
5
100
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
-5
-10
-15
-20
-25
-30
-35
-40
-45
-50
-55
-60
-65
-70
-75
-80
-85
-90
1
2