Application Bulletin - High Volume
Application Bulletin
EEMAX INC. 400 Captain Neville Drive, Waterbury, CT 06705 Tel. (800) 543-6163 Fax (203) 267-7890 WWW.EEMAX.COM
Challenge
• Long downtime between uses creates high storage costs
with large tanks
• Upsizing of natural gas lines and venting is difcult and
expensive
• Wide range of ow rates (0.5 GPM – 24 GPM) to feed up to
8 lavs, 8 showers, dishwasher and kitchen sink
• Need 70°F temperature rise
• Mechanical room located 100 ft from washrooms
Solutions
Eemax application engineers were engaged to specify the
system based on customer requirements. Tankless heaters are
piped in parallel then feed into a 120-gallon commercial tank
heater on a recirculation loop. The Eemax tankless units provide
heating when ow rate exceeds 4 GPM. The tank heater
provides hot water for the low ow needs and the recirculation
system. The result of pairing the tank and tankless heaters is
a best of both worlds solution minimizing storage losses while
delivering on-demand hot water.
Used qty (2) Eemax SpecAdvantage PhD AP096480 - 96 kW
(327,000 BTU/H), 480 volt, 140°F output temp.
Showers, Washrooms, and Kitchen at
Atlanta International Airport Customer Lounge
HIGH VOLUME DOMESTIC HOT WATER IN RETROFIT
OF HOSPITALITY SPACE
Eemax SpecAdvantage
Installer Benefits
• Quick product delivery
• Simple piping schematic created
by Eemax promotes proper
installation
• Utilizing electric heaters eliminates
gas lines and venting problems
• Labor savings with 70 lb tankless
heater vs 430 lb tank heater
User Benefits
• Tankless temperature output of
+/- 1°F
• Endless hot water
• Fast hot water delivery
Owner Benefits
• Small footprint compared to
multiple tanks creates more
usable oor space
• A low maintenance / long life
system resulting from low run
times
• Eliminating (3) 120 gallon tank
heaters saves over $1700 per year
in energy costs
• Installed costs comparable to
multi-storage tank system
EX09001-59 REV 11/2016