Application Bulletin - High Volume

Application Bulletin
EEMAX INC. 400 Captain Neville Drive, Waterbury, CT 06705 Tel. (800) 543-6163 Fax (203) 267-7890 WWW.EEMAX.COM
Challenge
Long downtime between uses creates high storage costs
with large tanks
Upsizing of natural gas lines and venting is difcult and
expensive
Wide range of ow rates (0.5 GPM – 24 GPM) to feed up to
8 lavs, 8 showers, dishwasher and kitchen sink
Need 70°F temperature rise
Mechanical room located 100 ft from washrooms
Solutions
Eemax application engineers were engaged to specify the
system based on customer requirements. Tankless heaters are
piped in parallel then feed into a 120-gallon commercial tank
heater on a recirculation loop. The Eemax tankless units provide
heating when ow rate exceeds 4 GPM. The tank heater
provides hot water for the low ow needs and the recirculation
system. The result of pairing the tank and tankless heaters is
a best of both worlds solution minimizing storage losses while
delivering on-demand hot water.
Used qty (2) Eemax SpecAdvantage PhD AP096480 - 96 kW
(327,000 BTU/H), 480 volt, 140°F output temp.
Showers, Washrooms, and Kitchen at
Atlanta International Airport Customer Lounge
HIGH VOLUME DOMESTIC HOT WATER IN RETROFIT
OF HOSPITALITY SPACE
Eemax SpecAdvantage
Installer Benefits
Quick product delivery
Simple piping schematic created
by Eemax promotes proper
installation
Utilizing electric heaters eliminates
gas lines and venting problems
Labor savings with 70 lb tankless
heater vs 430 lb tank heater
User Benefits
Tankless temperature output of
+/- 1°F
Endless hot water
Fast hot water delivery
Owner Benefits
Small footprint compared to
multiple tanks creates more
usable oor space
A low maintenance / long life
system resulting from low run
times
Eliminating (3) 120 gallon tank
heaters saves over $1700 per year
in energy costs
Installed costs comparable to
multi-storage tank system