Applications
• Eye/face wash
• Where tepid water is needed
• Multiple lavatories
• Restaurants and other food service requirements
• Booster applications
• Manufacturing and wash down processes
• Commercial and industrial
Performance Features
• Hot or cold water feed
• Available electrical models are 480V Delta (ED models) or
208V Delta (EX models) no neutral leg required
• Fitted with 1/2” compression fittings and electrical entry on
the bottom
• Built in over temp protection
• Flow switch activates heater only on demand (no standby
heat loss) – 99% efficient
• Save water – “Point of use application”
• Continuous hot water – no storage capacity to run out
• Factory set temperature available. Range ambient to 180°F
• Capacity to 5 GPM (T3 only), 4 GPM (T2T)
• Thermostatic control. Microprocessor provides precise outlet
temperatures
• Reduces calcification, liming and sedimentation
• Warranty – Five (5) years leaks and one (1) year on parts –
Field serviceable replaceable cartridge element, one (1) year
Optional Features
• Emergency eye/face wash ANSI Z358.1 (EE)
• Factory set ambient to 180°F (FS)
• Multi lavs 0.3 turn on. Staged up to 4 lavs 105°F-110°F temp
setting, aerators supplied (ML)
• Sanitation 180°F (S)
• N4, N4X (304SS) enclosures
Product Specifications:
Dimensions 15 1/4” x 12 1/4” x 4 1/4”
Weight 15 lbs.
Cover Powder Coated Steel
Color White
Element Triple replaceable Ni Chrome cartridge elements insert
Fittings 1/2” compression fittings at BOTTOM of unit
Pressure Min. 25 PSI, max. 150 PSI
U.S. Patent #’s: 4,762,980 and 4,960,976
Special Design Service
Inquiries for units for unique applications are welcome.
Call our Technical Service department at 1-800-543-6163.
Three Phase Series
Triple module, commercial/industrial thermostatic 3-phase heater
Specifications
Electric Tankless Hot Water Heater
The wetted surface of this product contacted by water
contains less than 0.25% lead and meets ANSI/NSF 372
Electrical configuration and requirements
All Eemax three phase units are custom made to order and as such, are non-
returnable and non-refundable. We urge you, therefore, to check your electrical supply,
making sure all criteria for operating your Eemax water heater are met.
Eemax 600v, 480v and 208v
Three Phase Units
Delta Configuration
Requires: 3 Lives and 1 Ground (earth)
L1
L2
L3
Suggested Specification
Tankless water heater shall be an Eemax “Three Phase” model
number _________________________.
Element shall be replaceable cartridge insert. Element shall be
iron free, Nickel Chrome material. Heater shall be fitted with
1/2” compression fittings. Heater shall be installed upright
with water connections on bottom. Hot water storage tanks
prohibited. Unit shall be Eemax or approved equal.
NOTE: Refer to rating chart for product information.
Enclosure to be fitted with the following features:
_____ EE Emergency Eyewash. Meets ANSI tepid water
requirements
_____ FS Factory Set. Customer specified factory-set not
to exceed temperature ambient to 180°F
_____ ML Multi lavs 0.3 GPM turn on, staged up to
4 lavs 105°F-110°F temp setting, aerators
supplied
_____ S Sanitation. Factory preset not to exceed
temperature of 180°F
_____ N4 NEMA 4 waterproof cabinet w/powder coat finish
_____ N4X NEMA 4 stainless steel waterproof corrosion-
resistant cabinet
Information and product specifications contained in this document are subject to change without notice.