Troubleshooting Guide

DISCONNECT ALL POWER TO UNIT BEFORE REMOVING
COVER.
STEP 1
ELECTRICAL CONNECTION
MODEL HA036240 IS SUPPLIED WITH A 8 PRONE TERMINAL BLOCK
MARKED (L1 L1) (L2 L2) (L3 L3)( L4 L4). MODEL HA027240 IS SUPPLIED
WITH A 6 PRONE TERMINAL BLOCK MARKED (L1 L1) (L2 L2) (L3 L3).
MODELS HA018240 AND HA024240 ARE SUPPLED WITH A 4 PRONE
TERMINALS BLOCK LABLED (L1 L1) (L2 L2)
EACH ONE OF THE CONNECTION SETS MUST BE CONNECTED TO AN IN-
DEPENDENT DOUBLE POLE 40 AMP BREAKER. L1-L1 GOES TO ONE 40 AMP
DOUBLE POLE BREAKER, L2-L2 GOES TO ANOTHER 40 AMP DOUBLE POLE
BREAKER AND L3-L3 TO ANOTHER 40 AMP DOUBLE POLE BREAKER, AND
L4 L4 TO ANOTHER 40 AMP DOUBLE POLE BREAKER NOTE: SPACE SAVING
BREAKERS WILL NOT OPERATE PROPERLY
YOU MUST ENSURE THE SET OF WIRES FROM EACH LEG ARE NOT CROSSED
AT THE BREAKERS OTHERWISE THE
UNIT WILL NOT FUNCTION AS
DESIGNED. IN ORDER TO MAKE SURE
THE WIRING IS CONNECTED
CORRECTLY PERFORM THE
FOLLOWING TEST.
DISCONNECT ALL BREAKERS AT THE
SERVICE PANEL. ONCE ALL BREAKERS
HAVE BEEN DISCONNECTED MEASURE
THE VOLTAGE GOING TO EACH ONE
OF THE SETS (L1 L1) (L2 L2) (L3 L3 )
(L4 L4) ALL SHOULD READ 0 VOLTAGE.
NOW TURN ON 1 BREAKER, IT DOES NOT MATTER WHICH ONE. ONCE ONE
BREAKER HAS BEEN TURNED ON, USING YOUR VOLTMETER PLACE ONE
PROBE ON L1 AND THE OTHER PROBE ON THE OTHER L1, MEASURE
ACROSS (L1-L1) YOU SHOULD GET A READING OF 208- 240V. DO THE
SAME FOR (L2-L2) AND (L3-L3) AND (L4 L4).
YOU MUST BE ABLE TO MEASURE
208/240 VOLTS ACROSS EACH SET
(L1 L1) (L2 L2) (L3 L3)(L4 L4) IF
YOU DO NOT THEN IT IS POSSIBLE
THE BREAKERS / WIRES ARE
CROSSED AND MUST BE
CORRECTED.
(EXAMPLE L1-L1 READS NO
VOLTAGE, BUT L1- L2 GIVES YOU
VOLTAGE READING)
PERFORM THIS VOLTAGE READING ON ALL LEGS OF TERMINAL BLOCK
BOTH AT THE BOTTOM AND TOP OF TERMINAL BLOCK TURNING ON 1
BREAKER AT A TIME.
IF POWER GOING TO THE UNIT IS NOT CORRECT, THE UNIT WILL NOT
OPERATE CORRECTLY, SO IT IS IMPORTANT TO PERFORM THIS TEST
FIRST, BEFORE PROCEEDING.
THE PROBLEM MIGHT NOT BE AT THE UNIT, BUT AT YOUR ELECTRICAL
PANEL, OR BREAKERS.
NOW THAT WE HAVE VERIFIED THAT THE ELECTRICAL CONNECTIONS
ARE CORRECT, LETS CONTINUE.